SUN2000-45KTL-US-HV-D0
User Manual
Alarm
Alarm ID
Name
106–113
Abnormal
String 1–8
120–127
String 1–8
Reversed
200
Abnormal
DC Circuit
Issue 04 (2018-06-01)
Alarm
Possible Cause
Severity
exceeds the inverter
maximum operating
voltage.
Cause ID = 4
The PV array is not
properly configured.
Excessive PV modules are
connected in series to PV
strings 7 and 8, and
therefore the PV string
open-circuit voltage
exceeds the inverter
maximum operating
voltage.
Warning
Cause ID = 1
The PV string is shielded
from sunlight for a long
time.
The PV string deteriorates
or is damaged.
Cause ID
Cause ID = 1
= 1:
The PV string is reversely
Major
connected.
Cause ID
Cause ID = 2
= 2:
Only a few PV modules are
Warning
connected in series to the
PV string, and therefore the
end voltage is lower than
that of other PV strings.
Major
Abnormal external conditions
trigger the protection for the
DC circuit inside the inverter.
The possible causes are as
follows:
Cause ID = 3
The inverter input is
disconnected accidentally,
or the PV string output
power changes sharply
because the PV string is
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 System Maintenance
Suggestion
modules connected in series to
PV strings 7 and 8 until the
open-circuit voltage is less than
or equal to the maximum inverter
operating voltage. After the PV
array configuration is corrected,
the inverter alarm disappears.
1. Check whether the PV string
current is obviously lower than
the currents of other PV strings.
2. If yes, check whether the PV
string is shielded from sunlight.
3. If the PV string is clean and not
shielded from sunlight, check
whether any PV module is faulty.
Cause ID = 1
Check whether the PV string is
reversely connected to the
inverter. If yes, turn off the two
DC switches after the PV string
voltage drops within the safe
voltage range (lower than 60 V
DC), and then correct the PV
string connection.
Cause ID = 2
Check whether the number of PV
modules connected in series to
the inverter is small. If yes,
increase the number.
Cause ID = 3/10/11
1. The inverter detects its external
working conditions in real time.
After the fault is rectified, the
inverter automatically recovers.
2. If the fault persists, contact
Huawei technical support.
Cause ID = 12/15
Turn off the AC output switch and
DC input switch. Then turn on the
AC output switch and DC input
108