Wiring; Wiring With Switch Apparatuss - ABB UMC22-FBP Technical Description

Fieldbusplug universal motor controller
Table of Contents

Advertisement

Universal Motor Controller UMC22-FBP
Software version 4.0
V 6
Chapter 3.2.1~1

3.2 Wiring

3.2.1 Wiring with switch apparatus
Hard-wire with switch apparatus and other components referring the application requirements.
Wiring examples see below and chapter 7.
Example: Direct starter
With parameter Control function = 3 (Direct starter):
the relay output DO0 is used to coltrol the motor contactor
With parameter Check-back = 1 (Auxiliary contacts):
the digital input DI0 is used to survey the contactor
(default: 2 (Motor current))
Fig. 3-1: UMC22-FBP as Direct starter (example)
FieldBusPlug / Issue: 02.2008
230 V
PTC inputs
T1
T2
T1
T2
5
DO
C
0 V
24 V
max.
200 mA
0
24
24
DI
V
V
V
0
10
11
12
13
0 V 24 V
24 V
supply
external
K1
inputs
supply
- 15 -
free outputs,
commands direct from fieldbus
N
DO1
DO2
690 / 400 V
K1
6
7
8
9
DO
DO
DO
DO
C
0
1
2
UMC22
DI
DI
DI
DI
DI
1
2
3
4
5
14
15
16
17
18
DI1
DI2
DI3
DI4 DI5
free inputs,
signals directly to the fieldbus
Short circuit
protection device
UMC22-FBP

Hide quick links:

Advertisement

Table of Contents
loading