4.3.4 Parameter - Details in alphabetical order

Remark
Parameter
Parameter value
name /
Parameter
number
Accessible only via Control Panel (menu point: Addr) or Addressing Set CAS21-FBP!
Enter slave address.
Address
Accessible only via control system!
Details see chapter 3.3.2.
Off
Address check
(0)
26
On
(1)
Accessible via control system or Control Panel (menu point: A.rES)!
Only for control function Overload relay due to safety considerations.
Automatic
Disabled
fault reset
(0)
11
Autoreset
(1)
Accessible only via control system!
Blocking
0-795 %
current
(0-159)
threshold
23
800 %
(160)
FieldBusPlug / Issue: 02.2008
Description of parameter values
Entering "999" results in "A---" = no valid address
-
*
* Range depends on the fi eldbus type
Address check off (= default):
-
UMC22 address is valid on fi eldbus.
Address check activated:
-
If the UMC22 and the FieldBusPlug contain different addresses the user
must decide.
Automatic fault reset off (= default):
AroF
Acknowledge via Control Panel or fi eldbus necessary to reset fault. To
switch on again, cooling time must be elapsed.
Automatic fault reset activated:
Aron
Automatic reset of fault when fault condition is off and cooling time has
elapsed. Fault is not monitored.
Blocking protection aktivated:
0-795 % x Set current (step: 5 %): 795 % = 5 % x 159
Fault signal when start-up time has elapsed and then current is above
threshold for > 1 s.
-
Remark:
Blocking sets the internal fault signal and the monitoring telegram bit
OVERLOAD and displays trip on the Control Panel. The cooling time is not
started.
Blocking protection off (= default):
-
800 % x Set current (step: 5 %): 800 % = 5 % x 160
Blocking protection is inactive.