Publication 1756-In604A-En-P - February - Allen-Bradley E Series Installation Instructions Manual

Controllogix controlnet interface module
Table of Contents

Advertisement

ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute
Backplane current
Isolation voltage
(continuous-voltage withstand
rating)
(1)
Wiring category
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications ControlLogix ControlNet Interface Module
1756-CNB, 1756-CNBR, Series E
Attribute
Operational temperature
Storage temperature
Relative humidity
Vibration
Operating shock
Nonoperating shock
Emissions
ControlLogix ControlNet Interface Module 31
Value
970 mA @ 5.1 V
1.7 mA @ 24 V
50V
Tested to 500V ac for 60 seconds
2 - on communications ports
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60 °C (32...140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
CISPR 11:
Group 1, Class A
Publication
1756-IN604A-EN-P - February 2006

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1756-cnb1756-cnbr