9.

Access Control

9.1

Access Control Options Settings

In the initial interface, press
It is used to set the parameters of the equipment control lock and related equipment.
Press Access Control Options on the Access Control interface.
Menu Item
Door Lock Delay (s)
Door Sensor Delay (s)
Door Sensor Type
Door Alarm Delay (s)
Speaker Alarm
VF Series User Manual
> Access Control to enter access control setting interface.
The time-period of unlocking (from door opening to closing automatically) after the
electronic lock receives an open signal sent from the device (value ranges from 0 to
When the door is opened, the door sensor will be checked after a time period; if the
state of the door sensor is inconsistent with that of the door sensor mode, alarm will
be triggered. The time period is the Door Sensor Delay (value ranges from 1 to 255
It includes Normal Open, Normal Close and None. None means door sensor is not
in use; Normal Open means the door is opened when electricity is on; Normal Close
means the door is closed when electricity is on.
When the state of the door sensor is inconsistent with that of the door sensor type,
alarm will be triggered after a time period; this time period is the Door Alarm Delay
(the value ranges from 0 to 999 seconds).
When the [Speaker Alarm] is enabled, the speaker will raise an alarm when the
Description
10 seconds)
seconds).
device is being dismantled.