Rustproofing or packing the casing with moisture absorb- ing material and covering the flanges is acceptable. When Design Envelope 4312 and 4392 twin pumps are handled in returning to service be sure to remove the drying agent from a similar manner to the normal twin pumping units. Extra the pump.
Discharge valve only must be used to reduce the All Design Envelope 4312 pumps contain a tapped hole in the pump flow, not the suction valve. motor bracket above the discharge flange for draining the Care must be taken in the suction line layout and well.
Page 6
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s fig. 1. 2 pipe mounted supported at ceiling fig. 1.5 floor saddle support Pipe hanger (typ.)
Design Envelope 4312 and 4392 vertical in-line install a tio n & twin pumping unit with ivs drive oper ating instr uctio n s fig. 1.8 tapped collection well on design do not envelope 4312 from sides Design Envelope 4312 seal leaks or condensate drain hole.
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 2 .3 . 2 supply fusing Since the leakage current is >3.5ma (approx...
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s fig. 2 . 2 Mains and grounding connections for a5 units fig.
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 2 .3 .5 electrical installation and control connections fig. 2 .7...
Digital Input Start Digital Input Pump Operating Mode Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive Common o pera t ing instr uct io n s...
Page 12
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s webserver configur ation Select Pump in the left side-menu...
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s 2. 4 design envelope pump 2 . 4 . 2 can bus wiring controller wiring Connections, Low, High, and Ground as per fig.
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 3 .0 networking controls For connection to the building automation system (ba s), the pump needs to be properly configured to the network.
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s 3 .1 modbus ip & rtu function code change...
Page 16
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s function code change start modbus # of data read...
Page 17
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s function code change start modbus # of data read...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 3 . 2 BACnet ip & ms/ tp object id object name...
Does not cover any damages to the equipment resulting from the suction piping. energize the motor momentarily and failure to observe the above precautions. Refer to Armstrong check that the rotation corresponds with the directional ar- General Terms and Warranty sheet. Contact your local row on the pump casing (clockwise when viewed from non- Armstrong representative for full information.
Check rotation arrow prior to operating the unit. The rotation of all Armstrong 4 20 0H & 4 28 0 Vertical In-Line units is clockwise when viewed from behind the motor (nde). important:...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 4 .3 . 4 gener al settings save save...
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s 4 .3 .5 manual /auto mode...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 4 .3 .6 pump control Activate Energy Performance Bundle...
Page 25
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s Single...
Page 26
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s Pressure Sensor Control Pump is now setup for Pressure...
Design Envelope 4312 and 4392 vertical in-line install a tio n & twin pumping unit with ivs drive oper ating instr uctio n s Pump is now setup for 2 Sensor Control Pump is now setup for Bypass Valve Control 4 .3 .7 alarms &...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 4 .3 .8 trend-gr aph There are 3 parameters that can be trended on the touch screen interface: •...
Design Envelope 4312 and 4392 vertical in-line install a tio n & twin pumping unit with ivs drive oper ating instr uctio n s 4 .3 .10 touch screen calibr ation If you are having issues with the touch screen, including: •...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 4 .3 .11 data logging Data logs can be used for energy performance analyses or to troubleshoot system issues. The data logs can be used with a building automation system (ba s) or for each standalone pump.
Design Envelope 4312 and 4392 vertical in-line insta l l a t io n & twin pumping unit with ivs drive op er atin g instr u ct io n s 4 . 4 web interface To access the control modes: Press settings ...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 5 .0 control modes 4 .5 design envelope flow readout toler ance 5 .1 constant flow...
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s 5 . 4 quadr atic curve control 5 .6 quadr atic curve control with...
Ensure that only the first and last terminating resistor switch- Parallel Sensorless Pump Control (pspc) pre-programmed in es are set to Enabled (towards the en label for the canbus the controls at Armstrong factories. For all other models (ex- port). cept twin pumps), pspc can be enabled aftermarket; please contact your local Armstrong factory for details.
5 .11 alternation indicator and that filter cartridges are replaced as recom- mended. (See Armstrong files 43 . 85 and 43 . 86 for seal Design Envelope Tango, dualARM, and Twin units are pre- environmental instructions). set to alternate lead-pump operation of each pump head to achieve equal run hours.
If mechanical seal environmental accessories are installed, ensure water is flowing through the sight flow indicator and that filter cartridges are replaced as recom- mended. (See Armstrong files 43 . 85 and 43 . 86 for seal environmental instructions). caution...
Design Envelope 4312 and 4392 vertical in-line in sta l l a t io n & twin pumping unit with ivs drive o pera t ing instr uct io n s c Remove the mechanical seal rotating assembly (8) shaft collar; the rotating assembly may be levered and raised-up in that manner.
Page 38
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s tions, File No. 6042.25, for removal of the motor shaft spring holder sleeve).
One or more of the parameters to control the vsd are not correct. Check the settings on the control card. If the alarm persists after cycling power to the pump, contact an Armstrong Technical Service representative. vsd startup An error occurred during the startup of the motor.
The voltage into the vsd is out of range. Verify that the correct voltage required to operate the voltage vsd is present by measuring each of the 3 phases. If the warning persists, contact an Armstrong Technical Service representative. Internal vsd An internal voltage generated by vsd is out of range.
Design Envelope 4312 and 4392 vertical in-line install a tio n & twin pumping unit with ivs drive oper ating instr uctio n s 8.0 fuse and wire recommendation table 1: ul fuses, 20 0 -240v ul compliance fuses frequency...
& Design Envelope 4312 and 4392 vertical in-line twin pumping unit with ivs drive o p era t i n g i n stru ction s 9.0 pump manager cloud smart Connect router to cloud...