Installation and operating instructions Design Envelope 4302 and 4382 IVS vertical in-line pumping unit with integrated controls File No: 94.82 eu Date: may 13, 2013 Supersedes: new Date: new...
1.0 uncr ating 2.0 installation Armstrong dualArm Design Envelope 4302 ivs and 4382 ivs 2.1 mechanical installation in-line pumps are thoroughly inspected before shipment to assure they meet with your order requirements. After remov- 2.1.1 location...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s installed in such a manner that the pump is not used as a Install a non-slam check valve in discharge line between pipe support.
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s warning Whenever any service work is to be performed on pumping unit, disconnect power source to driver.
Page 7
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s e Pipe work properly supported? note:...
Page 8
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s 5 Tighten set screw (11) to secure the locking handle (3)
Page 9
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s fi g. 1.2 Suction valve fi g. 1.3 Discharge valve fi...
Page 10
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s fig . 2 .3 Discharge elbow for minimum footprint fig . 2 .6 Additional fl oor support Pipe hanger (typ.)
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s 3 .0 ce conformities 4 .0 mechanical installation For Declaration of Conformity certifi...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s caution 5 .3 additional motor protection High voltage testing (Megging) of the motor / inverter With the exception of supply fuses / mcb’s to protect the...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s fi g. 4 Inverter Terminal Arrangement...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s x101 Terminals - Control Terminals i Sensorless Pressure Control - Connection Details The x101 terminals are used for analogue and digital signals that ivs Sensorless pumps are factory confi...
Page 15
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s iii Constant curve mode - bms speed control...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s 1st line shows up to 3 measurements continuously in normal 6.1 lcp functions and oper ation...
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s Control key functions 6.1. 4 display mode...
Page 18
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s Operating variables 1,1 and 1,2 and 1,3 in the fi rst line, and operat- ing variable 2 in the second line are selected via parameter 009, 010, 011 and 012.
Page 19
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s Parameter Groups This read-out state is standard after starting up or after initialisation.
Page 20
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s menu structur display mode menu mode quick menu mode choice of...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s 7.0 sensorless oper ation The probability of this occurring is remote but it is possible. One...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s The parameter list following this section gives typical settings 7. 2.1 setting par ameters for constant for closed loop control.
Page 23
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s Motor Settings – Parameters 101-141 Preset Reference 2 – Parameter 216 Set to 0% and not normally used.
Page 24
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s Quadratic Head – Parameter 705 group 6 – technical functions.
Page 25
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s descrip tion par ameter sensorless open loop...
Page 26
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s descrip tion par ameter sensorless open loop closed loop Time out...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s corrected. Reconnect the mains supply and reset (auto-reset by 9.0 warnings and alarms...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s wa r n i n g 6, voltage warning low (dc link voltage low):...
Page 29
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s fault finding chart - keypad available Pump won’t...
Page 30
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s fault finding chart - no keypad available Pump won’t Start...
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s The leakage current is of importance to safety during han- 10.0 integr ated controls...
Short circuit protection The inverter must be protected against short-circuit to avoid electrical or fi re hazard. Armstrong recommends using the fuses detailed in the separate ivs102 Operating Instructions to pro- tect service personnel or other equipment in case of an internal failure in the unit.
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s fig . 9 Relay connection terminals for c1 and c2 units 11.7 relay connections...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s 11.8 electrical installation and control connections fig . 10 Diagram showing all electrical connections...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s Control terminal functions and factory settings are 11.8.1 access to terminals...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s 11.8.3 connection examples ii closed loop – with sensor feedback ivs Sensorless pumps can be confi...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s iv.i constant curve mode - bms signal iv constant curve mode –...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s The number of the Active set-up (Sensorless mode being 12.0 progr amming, monitoring setup 1) is shown.
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s Alarm Log 12. 2 indicator lights (leds) Displays an Alarm list of the fi...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s The following parameter groups are accessible: The low water device input must be made for the pump to start in either hand mode or auto mode.
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s Readout and Programming of Indexed Parameters 12.
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s Par. 20-21 (Setpoint, h ) in units of pump head...
Design Envelope 4302 ivs and 4382 ivs vertical in sta l l a t io n & in-line pumping unit with integrated controls op er a t ing instr uct io n s 13 . 2 constant pressure control 13 .3 . 2 change to open loop (bas) control ivs Sensorless pumps can be confi...
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s Alarms that are trip-locked off er additional protection, means wa r n i n g /a l a r m 8 , dc under voltage: that the mains supply must be switched off before the alarm If the intermediate circuit voltage (dc) drops below the “volt-...
Page 45
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s a l a r m 1 6 , Short-circuit:...
Page 46
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s wa r n i n g 4 0 , Overload of Digital Output Terminal 2 7 :...
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s a l a r m 7 0 , Illegal Frequency Converter Confi guration:...
Page 48
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s table 1 Alarm/warning code list al arm al arm description...
Page 49
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s al arm/ trip description warning al arm/ trip...
Page 50
Design Envelope 4302 ivs and 4382 ivs vertical i nstall a ti o n & in-line pumping unit with integrated controls op erati n g i nstr ucti on s table 2 ivs 102 parameter settings setup 1 setup 2 setup 3 par.
Page 51
Design Envelope 4302 ivs and 4382 ivs vertical in stal l a t io n & in-line pumping unit with integrated controls o per ati n g i n struct i o n s setup 1 setup 2 setup 3 par.
Page 52