7.8.8.2 Setting Running Parameters

Because of permission restriction, log in as Advanced user. Choose Monitoring >
PID-SSC > Running Param. to enter the target page.
Figure 7-33 Setting running parameters
Parameter
Operation mode
Commissioning
output voltage

7.8.9 Custom Device

Custom Device: The SmartLogger can connect to the third-party devices supporting the
Modbus-RTU protocol, such as the box-type transformer and environmental monitoring
instrument (EMI). Since the protocol information points vary depending on vendors, you need
to obtain a protocol information file in .cfg format from Huawei and import the file into the
SmartLogger for successfully connecting to a third-party device.
Issue 12 (2019-01-15)
You can click the
tab on the tertiary navigation tree to query related information.
The Performance Data of the PID-SSC can be exported. When changing the name of the exported
file, retain the extension .tar.gz. Otherwise, the file will be unavailable.
Description
Specifies the current working mode of the PID module.
Specifies the output voltage when the PID module works in
commissioning mode. It is recommended that Commissioning
output voltage be set to a value greater than 250 V.
The SmartLogger supports the connection to a maximum of 10 types of custom devices and can connect
to multiple devices of the same type.
Copyright © Huawei Technologies Co., Ltd.
,
Set this parameter to Commissioning during commissioning
after deployment or fault locating. In this case, the PID-PVBOX
delivers the output voltage based on the value of the
commissioned output voltage.
Set this parameter to Normal after ensuring that the PID module
works normally.
7 WebUI
,