Basler BE1-BPR Instruction Manual

Basler BE1-BPR Instruction Manual

Breaker protection relay
Table of Contents

Advertisement

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BE1-BPR and is the answer not in the manual?

Questions and answers

Summary of Contents for Basler BE1-BPR

  • Page 2 INTRODUCTION This manual provides information concerning the operation and installation of the BE1-BPR Breaker Protection Relay. To accomplish this, the following is provided. Specifications Functional Description Installation Information Testing Procedures W A R N I N G ! TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY QUALIFIED PERSONNEL SHOULD PERFORM THE PROCEDURES PRESENTED IN THIS MANUAL.
  • Page 3 First Printing: December 1994 Printed in USA © 1995 - 1998 Basler Electric Co., Highland, IL 62249 December 1998 CONFIDENTIAL INFORMATION OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
  • Page 4: Table Of Contents

    CONTENTS SECTION 1 • GENERAL INFORMATION ........1-1 DESCRIPTION .
  • Page 5 CONTENTS - Continued SECTION 4 • FUNCTIONAL DESCRIPTION - Continued Keyboard ..........4-1 Serial Ports RS-232/RS-485 .
  • Page 6 BESTlogic APPLICATION HINTS ....... 5-8 BE1-BPR PREPROGRAMMED PROTECTION SCHEMES ... 5-9 Breaker Failure Logic 1 For Standard Relays (BFL1) .
  • Page 7 CONTENTS - Continued SECTION 7 • INSTALLATION - Continued MOUNTING ..........7-1 General .
  • Page 8: Section 1 • General Information

    Breaker failure relays are applied on a per breaker basis. That is, one breaker failure relay for each breaker in the substation. BE1-BPR relay outputs must be arranged to initiate the tripping of all the circuit breakers necessary to isolate the fault if the protected circuit breaker fails to operate. The relay may also need to initiate transfer tripping of remote breakers to accomplish this task.
  • Page 9: Breaker Reclosing

    A third major factor to be considered in reclosing is supervisory control. Supervisory control allows the operator to maintain control of the system at all times. BE1-BPR relays have two supervisory inputs (WAIT and LOCKOUT). WAIT stops the reclose sequence at any point and allows the sequence to continue when the WAIT input is removed.
  • Page 10: Failed Breaker Operation Required Timing Information

    If left undetected, severe damage to the breaker contacts could result. BE1-BPR relays can detect this type of fault using an extra low level phase overcurrent pickup and a long moving average filter. These features have been provided as standard features in the BE1-BPR relays.
  • Page 11: Application - Enhanced Models

    Fault Recording Enhanced model BE1-BPR relays can also be configured to record and save digital fault data for all three phases plus neutral (0 to 200 amperes) and the digital state of each input and output contact. Analog waveforms are digitized by sampling the waveforms at a periodic rate and converting the measured signals to digital values.
  • Page 12: Specifications

    Enhanced 19" Rack Mount 125/250 V ac/dc SPECIFICATIONS BE1-BPR Breaker Protection Relays have the following features and capabilities. Current Sensing Four isolated inputs with a maximum burden of less than 0.1 ohm. 5 Ampere CT Maximum continuous current: 20 amperes. Maximum one second current: 500 amperes.
  • Page 13 1 millisecond increments; 1 to 60 seconds in 0.1 second increments; or 1 to 3,600 cycles in 1 cycle increments. A setting of 0 will disable the timer. If programmed in cycles, the BE1-BPR relay will display the equivalent time in milliseconds.
  • Page 14 Front panel - RS-232, 9 pin, female, D-sub DCE Rear panel - RS-232, 9 pin, female, D-sub DCE; RS-485, 3 position terminal block Baud Rate: 300, 600, 1200, 2400, 4800, 9600, and 19.2 k (19,200) Buffer Size: 40 characters. BE1-BPR General Information...
  • Page 15 Type tested to withstand 2 g in each of three mutually perpendicular planes, swept over the range of 10 to 500 Hz for a total of 6 sweeps, 15 minutes each sweep, without structural damage or degradation of performance. Weight 12 pounds maximum BE1-BPR General Information...
  • Page 16: Section 2 • Application

    SECTION 2 • APPLICATION GENERAL BE1-BPR relays have seven inputs and five outputs plus an alarm output. There are three general purpose overcurrent fault detectors, six multipurpose timers, a three-shot recloser, and special outputs that are internally generated by the microprocessor. Using simple boolean expressions, the user can logically connect the various functional blocks to create a custom, application specific, logic scheme to handle special protection requirements.
  • Page 17: Instantaneous (50) Fault Detector Type 1

    A short dropout delay is advantageous for BF logic in order to allow for the minimum timing margin in critical applications. Figure 2-2 shows maximum dropout timing versus current input levels. BE1-BPR Application...
  • Page 18: Moving Average Filter Fault Detector Type 2

    MAF fault detector to pickup (or dropout), the RMS value of the average of the last 'n' cycles of current must be above (or below) the pickup setting. Typically, this filter is slow to pickup and slow to dropout but it is intended for use in low current applications where speed is not critical. BE1-BPR Application...
  • Page 19: Three-Phase Fault Instantaneous (50) Fault Detector Type 3

    The Type 2 fault detector’s moving average filter allows the BE1-BPR to discern the low level line charging current from random noise. The application of this fault detector is described in detail in the Breaker Arc Detector sub-section.
  • Page 20: General Purpose Timers

    Multiple Breaker Arrangements. In ring bus and breaker and a half bus applications, CTs from two breakers are often connected in parallel. If the BE1-BPR is connected to these CTs as shown in Figure 2-5, low fault detector pickup settings should be used with caution. In this...
  • Page 21: Timer Diagnostics

    A method to obtain and collect this data has been incorporated into the BE1-BPR relays. This method allows relative or absolute timing between any input, output or internal operation (i.e. timers, fault detectors) to be logged into a circular 40 event record.
  • Page 22: Trip Circuit Monitor Logic

    Breaker opens, trip circuit opened T C M Trip Circuit Monitor alarm output during the transition between the Relay drops out, trip bus floating TCM Timer Start closed and open states. Breaker closed TCM Timer Figure 2-10. Trip Circuit Monitor Timing Diagram BE1-BPR Application...
  • Page 23: Breaker Arc Detector

    TCM logic from working, even if the trip coil is open. In the case that the high impedance BFI sensing input of the BE1-BPR is connected directly to the trip bus, the TCM and the BFI impedances will be of similar magnitude causing the voltage to be divided nearly equally.
  • Page 24: Breaker Resistor Protection

    BFO, or to give an alarm. Breaker Resistor Protection Breaker resistor protection is a BE1-BPR relay feature that monitors the number of times a breaker opening resistor has been used and the amount of elapsed time between operations. If additional openings (operations) would exceed the resistor maximum power rating, the breaker resistor protection feature operates output 13 (O13), which can be used as a block reclose output.
  • Page 25: Breaker Failure Protection With Pre-Insertion Resistors

    This adaptive breaker failure logic can be configured by making use of the additional fault detectors and timers available in the BE1-BPR. One BF delay timer would be set to the maximum time allowed for the higher fault current level to be cleared and maintain system stability. The output would be ANDed with a fault detector set to detect this higher fault current level.
  • Page 26: Reclosing Functions

    Figure 2-14. Breaker Contact Duty Log Circuits Reclosing Functions A Reclosing Function is available in the BE1-BPR relay that can operate in parallel with the breaker failure logic. All inputs are programmable using the BESTlogic LR command. When reclosing is enabled, output 13 (O13) is designated at the reclose (close) output and can be connected to any physical output by using the LO command.
  • Page 27: Breaker Failure Logic 1 For Standard Relays (Bfl1)

    IN1 for breaker status, and OUT4 for the arc detector output. Refer to Application Data in this section for further details on the circuit operation. 5. Retrip Output. A Retrip output is provided to give a backup trip signal to the breaker trip coil. This can BE1-BPR Application 2-13...
  • Page 28: Breaker Failure Logic 2 For Standard Relays (Bfl2)

    3-phase BFI input active. For single-pole tripping, the phase pickup (PU1) must be set above maximum load levels. 3. Trip Coil Status Monitor. Preprogrammed logic is provided using IN1 to provide breaker status and IN2 2-14 BE1-BPR Application...
  • Page 29 5. Retrip Output. A RETRIP output is provided to give a backup trip signal to the breaker trip coil. This can either provide a separate path to a single trip coil or be hooked to the backup trip coil if available. 6. Alarm Output. An Alarm output is provided to signal relay failure or diagnostic alarm. BE1-BPR Application 2-15...
  • Page 30: Breaker Failure Logic 3 For Standard Relays (Bfl3)

    Three-phase BF logic is inhibited during this period because there is no 3-phase BFI input active. For single-pole tripping, the phase pickup (PU1) must be set above maximum load levels. 2-16 BE1-BPR Application...
  • Page 31 BE1-BPR Application 2-17...
  • Page 32 5. Retrip Output. A retrip output is provided to give a backup trip signal to the breaker trip coil. This can either provide a separate path to a single trip coil or be hooked to the backup trip coil if available. 6. Alarm Output. An Alarm output is provided to signal relay failure or diagnostic alarm. 2-18 BE1-BPR Application...
  • Page 33: Breaker Failure Logic 1 For Enhanced Relays (Bfl1E)

    5. Block Reclose Output. Preprogrammed logic is provided using breaker resistor protection output (O13) to drive the block reclose (BR) output (OUT3). Refer to Application Data in this section for further details on the circuit operation. BE1-BPR Application 2-19...
  • Page 34 7. External Fault Trigger. The enhanced BE1-BPR relay provides the ability to save the COMTRADE fault records for twelve events in memory at one time. An external fault trigger is provided to allow other multiple units to record the same event.
  • Page 35: Breaker Failure Logic 2 For Enhanced Relays (Bfl2E)

    3. Trip Coil Status Monitor. Preprogrammed logic is provided using IN1 to provide breaker status and IN2 for trip coil continuity. Refer to Application Data in this section for further details on the circuit operation. BE1-BPR Application 2-21...
  • Page 36 7. External Fault Trigger. The enhanced BE1-BPR relay provides the ability to save COMTRADE fault records for twelve events in memory at one time. An external fault trigger is provided to allow other multiple units to record the same event.
  • Page 37: Breaker Failure Logic 3 For Enhanced Relays (Bfl3E)

    3. Trip Coil Status Monitor. Preprogrammed logic is provided using IN1 to provide breaker status and IN2 for trip coil continuity. Refer to Application Data in this section for further details on the circuit operation. BE1-BPR Application 2-23...
  • Page 38 7. External Fault Trigger. The enhanced BE1-BPR relay provides the ability to save COMTRADE fault records for twelve events in memory at one time. An external fault trigger is provided to allow other multiple units to record the same event.
  • Page 39: Section 3 • Human-Machine Interface

    SECTION 3 • HUMAN-MACHINE INTERFACE Figures 3-1 and 3-2 show front panel sections for the human-machine interface (HMI). Figures 3-3 through 3-5 show BE1-BPR front and rear views. Table 3-1. Relay Indicators (Illustrated in Figure 3-1) Indicator Function GREEN LED that turns ON to indicate power supply is operational.
  • Page 40 If PROG key and then EDIT +/- key are pressed, the direction of the change is reversed until a new key other than +/- is pressed. Figure 3-2. BE1-BPR Controls (Switches) (Vertical Mount Not Shown) BE1-BPR Human-Machine Interface...
  • Page 41 Figure 3-3. BE1-BPR Relay, Horizontal Mount Front And Rear Views BE1-BPR Human-Machine Interface...
  • Page 42 Figure 3-4. BE1-BPR Relay, Vertical Mount Front View BE1-BPR Human-Machine Interface...
  • Page 43 Figure 3-5. BE1-BPR Relay, Vertical Mount Rear View BE1-BPR Human-Machine Interface...
  • Page 44: Section 4 • Functional Description

    SECTION 4 • FUNCTIONAL DESCRIPTION GENERAL BE1-BPR Breaker Protection Relays are microprocessor-based devices that provide breaker failure pro- tection, optional fault recording, and diagnostic monitoring of breaker wear and breaker resistor overheating. This section describes the hardware and software functional descriptions.
  • Page 45: Circuit Operation

    The isolated switching power supply generates ±12 Vdc, +5 Vdc, and an isolated +5 Vdc. If the +5 Vdc digital supply falls outside the defined tolerance, then the microprocessor will be reset by the power supply supervisory circuit. This reset takes the relay off-line and lights the ALARM LED. BE1-BPR Functional Description...
  • Page 46: Watchdog Timer

    Section 5, BESTlogic Programmable Logic . Outputs There are five types of outputs from the BPR relay. They are: ALARM Relay Output Relays Targets LCD Display Serial Ports RS-232/RS-485 BE1-BPR Functional Description...
  • Page 47: Alarm Relay

    Figure 4-2 shows the menu progression from start-up to maintenance for an enhanced BE1-BPR. Figure 4-3 shows the menu progression for a standard BE1-BPR. The operator uses the right arrow key to scroll through the available menu screens and the down arrow key to access menu sub-screens. When using a communication port, the relay is programmed using ASCII software commands.
  • Page 48: Startup And Menu Selection

    For now, let's assume that we have not enabled password protection. An access level screen will be displayed momentarily showing your programming access level and then the original display will return and a cursor will be visible. BE1-BPR Functional Description...
  • Page 49 Figure 4-2. Enhanced BE1-BPR Menu Display Screens BE1-BPR Functional Description...
  • Page 50 Figure 4-3. Standard BE1-BPR Menu Display Screens BE1-BPR Functional Description...
  • Page 51: Selecting Menu Screen

    +/- key to select Y for yes. Press PROG key and the relay will go off-line for 1-2 seconds while the new settings are saved and the BPR relay re-initializes itself. Figure 4-4. Accessing PROGRAM Mode from HMI BE1-BPR Functional Description...
  • Page 52: Changing Parameters Using Communication Ports

    Entering N exits the programming mode without saving changes and returns the relay to an on-line condition. BE1-BPR Functional Description...
  • Page 53 Figure 4-5. Exiting PROGRAM Mode From HMI Settings changes made during a programming session can be discarded by using the QUIT command. The QUIT command will restore all settings, exit the programming mode, and return the relay to the on-line condition. 4-10 BE1-BPR Functional Description...
  • Page 54: Password Protection

    CHANGES LOST RELAY ON-LINE Password Protection BE1-BPR relays provide password protection against unauthorized changes to relay setting parameters and operating registers. Four different passwords of one to eight characters may be used. Each password provides a different access capability. Gaining write access in an access area with password protection requires that the correct password be entered.
  • Page 55 1, 2, 3 PHOLD Set output hold timers 1, 2, 3 PTLOG Set timer log operation 1, 2, 3 SNAME Set substation and circuit name for COMTRADE reports 1, 4 Override output logic and pulse output contacts 4-12 BE1-BPR Functional Description...
  • Page 56: Entering An Access Password At The Front Panel

    The menu screen most often viewed is the TARGETS screen. Because of that, the TARGETS screen is the default screen. Viewing order or progression through the menu screens is based on the expected frequency of use. BE1-BPR Functional Description 4-13...
  • Page 57: Targets Screen

    (fault log) the source of the target has been tlog (timer log) cleared. Data can be cleared diag (relay diagnostics) through the HMI by viewing the data on the HMI screen and pressing the Reset key. 4-14 BE1-BPR Functional Description...
  • Page 58: Relay Setup

    BE1-BPR relays with standard options have three preprogrammed breaker failure logic schemes that are stored in non-volatile program memory. BE1-BPR relays with enhanced options have six preprogrammed breaker failure logic schemes that are stored in non- volatile program memory.
  • Page 59: Transformer Ratios

    A value of 5 is reported for units with 5 ampere CTs and a value of 1 is reported for units with 1 ampere CTs. This setting is factory programmed and is not user adjustable. 4-16 BE1-BPR Functional Description...
  • Page 60: Fault Detectors

    CTN=80 Fault Detectors Three fault detectors, F1, F2, and F3, are provided in the BE1-BPR. Each fault detector can be configured for phase or neutral current sensing and the type of filtering. Three filtering options are available: Instantaneous (Type 1), Moving Average (Type 2), and Instantaneous Three Phase (Type 3).
  • Page 61 (Lfx=type,2). See LF command information in BESTlogic Functions section. An access area one or two password is required to change settings. PU Command Examples 1. Set the analog channel pickup level at 6.2 amperes. PU1=6.2 2. Read the pickup setting for all channels. PU1=6.2; PU2=0.5; PU3=0.1,10 4-18 BE1-BPR Functional Description...
  • Page 62: Timers

    Timers Six independent timers are provided in the BE1-BPR. Each timer consists of a time delay setting (TD[x]), a start input, a reset input, and an output (T[x]). Timing starts when the start input is true and the reset input is false. The timer runs for the duration of the time delay setting unless the reset input becomes true.
  • Page 63: Reclosing

    Reclosing A Reclosing Function is provided in the BE1-BPR relay that can operate in parallel with the breaker failure logic. All inputs are programmable using the BESTlogic LR command. When reclosing is enabled, virtual output 13 (O13) is used for the 79 Close output of the recloser function block. If reclosing is disabled, O13 is used for the breaker resistor protection function output that is described in the Breaker Status sub-section.
  • Page 64 Stops the reclose sequence at any point. The reclose sequence is inhibited as long as the wait input is present. When the wait input is removed, the sequence continues from the point that it was stopped. Figure 4-7. Reclosing Logic Circuit BE1-BPR Functional Description 4-21...
  • Page 65 TYPE in the LR command to 0, 1, or 2. NOTE After the programmable logic is changed or the time delay settings are changed, the recloser initializes as described in the Reclosing Mode, TYPE 1 or TYPE 2 . 4-22 BE1-BPR Functional Description...
  • Page 66: Output Hold Function

    PHOLD Command Purpose: Read or program the output hold timer mask. Syntax: PHOLD[=<#####>] Comments: Access area password one, two, or three required to change settings. Default setting is 11111. BE1-BPR Functional Description 4-23...
  • Page 67: Relay Status

    This command returns all current input values and system status registers. The status registers indicate the state of contact sensing inputs I1 through I7, timers/counters T1 through T6, fault detectors F1 through F3, outputs OA, and O1 through O15, recloser status, breaker status, and any active diagnostic flags. 4-24 BE1-BPR Functional Description...
  • Page 68 No access area password is required for reporting functions. Primary and secondary current values are available through HMI menu branch 2. I Command Examples 1. Read Phase B current. 3.23KA 2. Read all primary currents. IA=3.23KA; IB=3.23KA; IC=3.23KA; IN=0.00KA BE1-BPR Functional Description 4-25...
  • Page 69 Access area level password one, two, or three is required to change settings. A diagnostic flag is enabled by a 1 and disabled by a 0. DIAG1 drives virtual output 14 (O14) and DIAG2 drives virtual output 15 (O15). Entering PDIAG returns the diagnostic mask for O14 and O15. 4-26 BE1-BPR Functional Description...
  • Page 70 Reads diagnostic data. Syntax: TEST Comments: No access area password is required to read diagnostic data. TEST Command Example Verify the software checksum. TEST RELAY ON-LINE DIAG: 1 OF 2 CLOCK NOT SET PROGRAM CHECKSUM: 3C7E BE1-BPR Functional Description 4-27...
  • Page 71: Breaker Status

    Breaker Contact Duty Diagnostics (Enhanced Relays Only) Breaker contact duty log, DLOG, is stored in non-volatile memory and contains the approximate duty or contact wear on each pole (phase) of the breaker represented as a percentage of a maximum, DMAX. A 4-28 BE1-BPR Functional Description...
  • Page 72 DLOG Breaker contact duty log data HMI Menu Branch: 3 Parameter Unit of Measure Range Increment Default percent 0.00 to 101.00 0.01 0.00 DLOG HMI Screen Example BE1-BPR Functional Description 4-29...
  • Page 73 P = breaker pole A, B, or C YY = accumulated breaker pole duty as a percent of the DMAX setting This function is available on enhanced BE1-BPR relays only. An access area one or three password is required to change settings.
  • Page 74: Breaker Operations Counter

    This reset period must occur before another operation can safely be allowed. The BE1-BPR keeps track of the accumulated resistor heating by adding one operation to the RESOPS counter for every breaker opening and subtracting one from the RESOPS counter, <reset>...
  • Page 75 Read or change breaker resistor monitoring data. Syntax: BKRRES[=<MAXOPS>,<reset>,<Ires>] Comments: An access area one or three password is required to change settings. BKRRES Command Example Set Ires at 500 amperes, reset_time at 15 minutes, and MAXOPS at 4. BKRRES=4,15,500 4-32 BE1-BPR Functional Description...
  • Page 76: Timer Log

    TD1=100 Sets timer TD1 at 100 milliseconds. TD1 starts timing when IN2 is energized. When O7 goes low, the difference in time between the TD1 setting and O7 going low is recorded in the timer log. BE1-BPR Functional Description 4-33...
  • Page 77 A diagnostic alarm is logged if logic becomes true inside (alm_type L) or outside (alm_type H) this time window. alm_time units can be milliseconds (default), seconds (s), or cycles (c). Figure 4-11 illustrates an example of an H alarm and L alarm condition. 4-34 BE1-BPR Functional Description...
  • Page 78: Fault Log (Enhanced Relays Only)

    255, the fault log number automatically returns to 1 and starts again. If the fault memory is full, the oldest record is replaced by the latest one acquired. The fault log data records are reset to zero at power-up or when the FLOG=0 command is given. BE1-BPR Functional Description 4-35...
  • Page 79: Fault Log Listing

    Reads a listing of all fault records, reads summary information about any individual fault record or clears all fault records. Syntax: FLOG[#][=0] Comments: This function is available on enhanced BE1-BPR relays only. No access area password is required to read or reset fault log data. FLOG Command Example Read fault log 125. FLOG125...
  • Page 80: Fault Summary

    Reads or changes the trigger logic or triggers a fault record. Syntax: TRIGGER[=<logic term>/Y] Comments: This function is available on enhanced BE1-BPR relays only. Access area password one, two, or three is required to change settings. No password access is needed to trigger a fault record. BE1-BPR Functional Description...
  • Page 81 Obtains a COMTRADE fault report. Syntax: FLT<#><type> Comments: This function is available on enhanced BE1-BPR relays only. No access area password is required to retrieve a COMTRADE fault report. FLT Command Examples 1. Initiate the transfer of the configuration file for fault 155.
  • Page 82: Downloading Comtrade Files

    Default HMI display screen (PDISPLAY) Output contact testing (OUT) Software version reporting (VER) Examples of typical MAINTENANCE menu screens are shown below. MAINTENANCE menu screen 0$,17(1$1&( Sub-screen 1 7,0( '$7( $  Sub-screen 2 &20 ) &20 5 1 1 BE1-BPR Functional Description 4-39...
  • Page 83: Time And Date

    Reads or changes the time clock. Syntax: TIME [=<hr>:<mn><f><sc>.<msc>] Comments: No access is required to change settings. TIME Command Examples 1. Read the current time (12 hour format). TIME 11:24P45.339 2. Set the time clock at 11:24 pm. TIME=11:24P00 4-40 BE1-BPR Functional Description...
  • Page 84 PCLK Command Examples 1. Read the clock format. PCLK PCLK=D,12 2. Program the clock format so that the date is displayed with the month preceding the date and time is displayed in the 24 hour format. PCLK=M,24 BE1-BPR Functional Description 4-41...
  • Page 85: Communications Settings

    BE1-BPR relays that are connected to an IRIG-B source will automatically synchronize the time and date with the IRIG-B source. However, the year must be set manually since it is not included in the IRIG-B data stream. Once all components of the time and date are received by the relay, the front panel CLOCK LED will turn off to indicate that the clock has been set.
  • Page 86: Programming A New Password

    (one to eight characters) and the desired access area (F/R/B). Press and hold the PROG key to exit the programming mode. At the SAVE screen, release PROG and enter Y to save the changes. Press PROG again to return to the MAINTENANCE menu. BE1-BPR Functional Description 4-43...
  • Page 87: Calibrating The Analog Channels

    The power system frequency can be read or changed from the CAL menu or by using the FREQ command through the communications port. Section 8, Calibration and Testing provides detailed information about analog channel calibration. 4-44 BE1-BPR Functional Description...
  • Page 88 Reads or changes the nominal power system frequency information used by the relay. Syntax: FREQ [=<freq(hz)>] Comments: Access area password one is required to change the setting. FREQ Command Examples 1. Read the frequency setting. FREQ 2. Change the frequency setting to 50 hertz. FREQ=50 BE1-BPR Functional Description 4-45...
  • Page 89: Lcd Contrast Adjustment

    = A (OUTA), 1 (OUT1), 2 (OUT2), 3 (OUT3), 4 (OUT4), OR 5 (OUT5) Entering OUT=1 or OUT=0 will pulse on or pulse off all outputs. Access area one or four password is required to test outputs. 4-46 BE1-BPR Functional Description...
  • Page 90: Firmware Version Display

    HMI is limited to the relay model number and software version number. VER Command Example Obtain the program version, part number, and serial number of the relay. Model : BE1-BPR Program : VER 2.23E : 9 2720 00 101 : UHG9827-001 BE1-BPR Functional Description 4-47...
  • Page 91: Section 5 • Bestlogic Programmable Logic

    Basler Electric Standard Trip_logic (BESTlogic), is a flexible and user friendly programming language for controlling specific BE1-BPR relay outputs based on combinations of inputs, timers, and outputs. It is not necessary to change logic circuits in the relay hardware to meet changing needs in your system environment.
  • Page 92: Logic Variables

    Input Contact 2 TB1: 17, 18 Input Contact 3 TB1: 19, 20 Input Contact 4 TB1: 21, 22 Input Contact 5 TB1: 22, 23 Input Contact 6 TB1: 24, 25 Input Contact 7 TB1: 25, 26 Timer 1 Timer 2 BE1-BPR BESTlogic...
  • Page 93 Virtual Output 14 Virtual Output 15 Fault Detector Outputs are controlled by the CT phase inputs, IA (terminals 1, 2), IB (terminals 3, 4), IC (terminals 5, 6), or by the CT neutral input, IN (terminals 7, 8). BE1-BPR BESTlogic...
  • Page 94 Figure 5-1. BESTlogic Function Blocks BE1-BPR BESTlogic...
  • Page 95: Logic Names

    Read the name of the active logic. BFL1 OUTPUT OPERATIONS The BE1-BPR relay provides two types of outputs: virtual outputs and hardware outputs. The following paragraphs provide information about the function and characteristics of virtual and hardware outputs. Virtual Outputs A virtual output exists only as a logical state inside the relay.
  • Page 96: Hardware Outputs

    Functional Description provides information about the settings associated with these functions. Hardware Outputs A hardware output is a physical relay contact that can be used for protection or control. The BE1-BPR relay has five isolated, normally open (N.O.) output contacts (OUT1-OUT5) and one isolated normally closed (N.C.) alarm output.
  • Page 97: Output Programming Examples

    LI[n] de-bounce time (db) before a new state can be recognized. Each contact input has a logical mode of operation (LI[n]) that defines the contact input operating characteristics. BE1-BPR BESTlogic...
  • Page 98: Bestlogic Application Hints

    OUT2 (O2) = Secondary BFO OUT5 (O5) = Retrip Output TIMER1 (T1) = Always associated with primary BFO delay timer TIMER2 (T2) = Always associated with alternate BFO delay timer TIMER3 (T3) = Always associated with the control timer BE1-BPR BESTlogic...
  • Page 99: Be1-Bpr Preprogrammed Protection Schemes

    Extra care is required to make sure this is done and that the short is removed once the electronics are reinstalled. BE1-BPR PREPROGRAMMED PROTECTION SCHEMES Each BE1-BPR relay comes with a number of preprogrammed breaker failure logic schemes that are preprogrammed into non-volatile memory. Section 2, Application contains descriptions of the logic schemes and their applications.
  • Page 100: Breaker Failure Logic 1 For Standard Relays (Bfl1)

    LR=0,0,0,0,0 LO2=T2 LO11=0 LF3=PI,2 LT1=D,O8,/O8 LO3=T1O7 LO12=F3I1 LI1=4,12 LT2=D,O9,/O9 LO4=T5 LI2=4,12 LT3=0,0,0 LO5=O8+O9 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=I3+I4+I5 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. 5-10 BE1-BPR BESTlogic...
  • Page 101: Breaker Failure Logic 2 For Standard Relays (Bfl2)

    LR=0,0,0,0,0 LO2=O3 LO11=I3+I4+I5 LF3=PI,2 LT1=D,O8,/O8 LO3=T1O7+F1T2+O1O7 LO12=F3I1 LI1=4,12 LT2=D,O9,/O9 LO4=T5 LI2=4,12 T3=C,O10,/O10 LO5=T3 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=T3O11 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. BE1-BPR BESTlogic 5-11...
  • Page 102: Breaker Failure Logic 3 For Standard Relays (Bfl3)

    LR=0,0,0,0,0 LO2=O3 LO11=I3+I4+I5+O8 LF3=PI,2 LT1=D,O8,/O8 LO3=T1O7+F1T2+O1O7 LO12=F3I1 LI1=4,12 LT2=D,O9,/O9 LO4=T5 LI2=4,12 LT3=O10,/O10 LO5=T3 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=T3O11 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. 5-12 BE1-BPR BESTlogic...
  • Page 103: Breaker Failure Logic 1 For Enhanced Relays (Bfl1E)

    LF2=NI,1 LR=0,0,0,0,0 LO2=T2 LO12=F3I1 LF3=PI,2 LT1=D,O8,/O8 LO3=O13 LI1=1,12 LT2=D,I6,/I6 LO4=T5 LI2=1,12 LT3=0,0,0 LO5=O8+I6 LI3=1,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=1,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=1,12 LT6=0,0,0 LO8=I3+I4+I5 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. BE1-BPR BESTlogic 5-13...
  • Page 104: Breaker Failure Logic 2 For Enhanced Relays (Bfl2E)

    LR=0,0,0,0,0 LO2=T1O7+F1T2+O1O7 LO11=I3+I4+I5 LF3=PI,2 LT1=D,O8,/O8 LO3=O13 LO12=F3I1 LI1=4,12 LT2=D,O9,/O9 LO4=T5 LI2=4,12 LT3=C,O10,/O10 LO5=T3 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=T3O11 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. 5-14 BE1-BPR BESTlogic...
  • Page 105: Breaker Failure Logic 3 For Enhanced Relays (Bfl3E)

    LR=0,0,0,0,0 LO2=T1O7+F1T2+O1O7 LO11=I3+I4+I5+O8 LF3=PI,2 LT1=D,O8,/O8 LO3=O13 LO12=F3I1 LI1=4,12 LT2=D,O9,/O9 LO4=T5 LI2=4,12 LT3=O10,/O10 LO5=T3 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=T3O11 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. BE1-BPR BESTlogic 5-15...
  • Page 106: Programming Custom Protection Schemes

    4. Review the changes using LINF0 <new_name> or the LF, LI, LT, and LO commands. 5. If the new logic is to become the active logic, then type LOGIC=<new_name>. 6. Use the SAVE command to save the customized logic scheme. 5-16 BE1-BPR BESTlogic...
  • Page 107: Custom Application Examples

    LR=0,0,0,0,0 LO2=T1O7+T2F3 LO11=0 LF3=PI,2 LT1=D,O8,/O8 LO3=T1O7+T2F3 LO12=F3I1 LI1=4,12 LT2=D,O8,/O8 LO4=O14 LI2=4,12 LT3=0,0,0 LO5=O8 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=0,0,0 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=I3+I4+I5 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. BE1-BPR BESTlogic 5-17...
  • Page 108: Breaker Failure Logic With Reclosing (Bf+79)

    Breaker Failure Logic With Reclosing (BF+79) LN=BF+79 LI6=4,12 LOA=T4+O15 LO9=0 LF1=PI,1 LI7=4,12 LO1=T1O7+T2 LO10=O5+T5 LF2=NI,1 LR=1,O10,/I1,I6,O11 LO2=T2+T2 LO11=I7+O1 LF3=PI,2 LT1=D,O8,/O8 LO3=O13 LO12=F3I1 LI1=4,12 LT2=D,I5,/I5 LO4=O14 LI2=4,12 LT3=0,0,0 LO5=O8+I5 LI3=4,12 LT4=D,O6,/O6 LO6=/I1/I2 LI4=4,12 LT5=D,O12,/O12 LO7=F1+F2 LI5=4,12 LT6=0,0,0 LO8=I3+I4 5-18 BE1-BPR BESTlogic...
  • Page 109 The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm output. Note: Breaker resistor protection is included in the logic scheme only if the BKRRES command is entered. BE1-BPR BESTlogic 5-19...
  • Page 110: Section 6 • Communications

    For a free copy of BESTview for Windows , contact the Customer Service Department of the Basler Electric Power Systems Group at 618-654-2341.
  • Page 111: Command Format

    One or more spaces may be added between entries for clarity if desired Commands received by the BE1-BPR relay consist of two general types: requests for information and changes to operating parameters. Requests for information will always be accepted and executed, however changes to operating parameters may be limited to access from personnel with the proper password.
  • Page 112: Creating Settings Files

    BKROPS=,I1 BKRRES=0,0,0.000E+00 The following procedure describes how relay settings can be read, modified, saved to a file, and uploaded to BE1-BPR relays. Any commercially available communications software may be used. Instructions for configuring Windows 95 HyperTerminal and Windows Terminal are provided in Appendix A, Terminal ®...
  • Page 113: Commands

    SAVE;Y followed by a carriage return. The text file containing the settings can be uploaded to any BE1-BPR relay using the communications software that was used to view the relay settings.
  • Page 114 Section 4, Functional Description, Relay Status DLOG Command (Enhanced Relays Only) Purpose: Reads or changes breaker contact duty log data. Syntax: DLOG[P][=<YY>] Reference: Section 4, Functional Description, Breaker Status, Breaker Contact Duty Diagnostics (Enhanced Relays Only) FLOG Command (Enhanced Relays Only) BE1-BPR Communications...
  • Page 115 Reads the name of the active logic or program a new set of logic equations called <name>. Syntax: LN[=<name>] Reference: Section 5, BESTlogic Programmable Logic, Logic Names LO Command Purpose: Reads or programs output logic. Syntax: LO [#[=<Boolean equation>]] Reference: Section 5, BESTlogic Programmable Logic, Programming Output Operational Characteristics LOGIC Command BE1-BPR Communications...
  • Page 116 PDISPLAY[=<default_menu>,<default_screen>] Reference: Section 4, Functional Description, Software Functional Description, Maintenance, Default HMI Display Screen PHOLD Command Purpose: Reads or programs the output hold timer mask. Syntax: PHOLD[=<#####>] Reference: Section 4, Functional Description, Software Functional Description, Relay Setup, Reclosing BE1-BPR Communications...
  • Page 117 Section 4, Functional Description, Software Functional Description, Fault Log (Enhanced Relays Only), Data Acquisition STATUS Command Purpose: Returns a report of inputs, outputs, and internal relay status. Syntax: STATUS Reference: Section 4, Functional Description, Software Functional Description, Relay Status BE1-BPR Communications...
  • Page 118 Section 4, Functional Description, Software Functional Description, Fault Log (Enhanced Relays Only), Oscillographic Data Acquisition VER Command Purpose: Returns information about relay hardware and software. Syntax: Reference: Section 4, Functional Description, Software Functional Description, Maintenance, Software Version Display BE1-BPR Communications...
  • Page 119: Section 7 • Installation

    Dielectric Test . If a wiring insulation test is required on the switchgear or panel assembly of which this unit is a part, see Dielectric Test below. Be sure that the BE1-BPR case is hard wired to earth ground using the ground terminal on the rear of the unit.
  • Page 120 Figure 7-1 Overall Dimensions Figure 7-2. Cutout Dimensions (Panel Mount) BE1-BPR Installation...
  • Page 121 Figure 7-3. Overall Dimensions (Vertical Mount) BE1-BPR Installation...
  • Page 122 Figure 7-4. Overall Dimensions, Side View (Vertical Mount) BE1-BPR Installation...
  • Page 123 Figure 7-5. Panel Drilling Diagram (Vertical Mount) BE1-BPR Installation...
  • Page 124: Installing Escutcheon Plates

    Horizontal Mount To install the escutcheon plate kit (Basler part number, 9 2720 13 100) you must first remove the mounting flanges by removing the four screws (1) from the relay (two from each side). To allow the escutcheon plate to slide onto the relay, remove the four screws (4) from the relay (two from each side).
  • Page 125: Connections

    Incorrect wiring may result in damage to the unit. Typical external sensing connections are shown in Figure 7-8. Connections for BE1-BPR relay terminals are identified in Figure 7-9. Terminals are suitable for use with wire sizes 12 AWG or larger.
  • Page 126: Communication Connectors And Settings

    Table 7-1. RS-232 Pinouts (Port0 And Port1A) Function Name Direction SHIELD ---- TRANSMIT DATA (TXD) FROM RELAY RECEIVE DATA (RXD) INTO RELAY ---- SIGNAL GROUND (GND) DCE READY (DSR) FROM RELAY CLEAR TO SEND (CTS) INTO RELAY REQUEST TO SEND (RQS) FROM RELAY ---- BE1-BPR Installation...
  • Page 127 Figure 7-10. Protective Relay Terminal (PRTU) to BE1-BPR Figure 7-11. Personal Computer to BE1-BPR Cable BE1-BPR Installation...
  • Page 128 Figure 7-12. RFL 9660 Protective Relay Switch to BE1-BPR Cable Figure 7-13. SEL-2020 Communications Processor to BE1-BPR Cable 7-10 BE1-BPR Installation...
  • Page 129: Rs-485 Connections

    COMx command through the communication port with the initial settings set for the proper mode as shown in the front panel maintenance menu. Figure 7-14. RS-422/RS-485 DB-37 to BE1-BPR Cable Connection BE1-BPR Installation...
  • Page 130: Irig-B Connections

    IRIG-B Connections The IRIG-B connections are located on a terminal block shared with the RS-485 terminals. Terminal designations and functions are shown in Table 7-3. Table 7-3. IRIG-B Pinouts Terminal Function – REFERENCE SIGNAL 7-12 BE1-BPR Installation...
  • Page 131: Section 8 • Calibration And Testing

    Connect all current inputs (A, B, C, and N) in series with the AC current source and apply power to the relay. Step 2. Use the front panel keys to select the fourth sub-screen of the MAINTENANCE menu branch. Adjust the system frequency for 50 or 60 hertz. FREQ RANGE-1L/2H BE1-BPR Calibration And Testing...
  • Page 132: Operational Test Procedure

    Select the logic scheme desired from the standard schemes available or define and select a new scheme as required. A. Selecting preprogrammed (pre-defined) scheme by entering the following commands: >ACCESS=<password> or ACCESS=BPR if password not used. >LOGIC=<name of preprogrammed scheme> >SAVE ARE YOU SURE (Y/N)? - Y RELAY OFF-LINE BE1-BPR Calibration And Testing...
  • Page 133: Entering Settings

    Step 5. Enter the PickUp settings, using the PU command. Step 6. Enter the Time Delay settings, using the TD and TD79 commands. Step 7. Program the format of the real-time-clock by using the PCLK command. BE1-BPR Calibration And Testing...
  • Page 134: Operational Testing

    Record the relay serial number, part number, logic, and operational settings for future reference. This can be done easily with any standard communication program by opening a file and then saving the relay response to the VER and SHOWSET commands. BE1-BPR Calibration And Testing...
  • Page 135: Section 9 • Maintenance

    Depending on the criticality of the application, and the redundancy of the protection system, a draw-out assembly from a spare BE1-BPR relay can be inserted into the mounted and wired case assembly to restore protection. The relay requiring service can then be returned to the factory in the case from the spare relay.
  • Page 136: Section 10 • Manual Change Information

    Section 8. Updated the manual style and added an index. Revised the manual to change pg. 1-7 Output Relay Pickup 1046 12-10-98 Time , Output 1 from “1/4 cycle (4.2 milliseconds) maximum” to “4 milliseconds typical, 5 milliseconds maximum.” BE1-BPR Manual Change Information 10-1...
  • Page 137 $33(1',;$x7(50,1$/(08/$7,21 £ £ This appendix provides instructions for configuring Windows 95 HyperTerminal and Windows Terminal to communicate with your BE1-BPR relay. £ WINDOWS 95 HYPERTERMINAL Step 1. Click Start: Highlight Programs, Accessories, HyperTerminal. Step 2. Click HyperTerminal to open the folder.
  • Page 138: Appendix A • Terminal Emulation

    Step 1. In Program Manager, open the Accessories program group and double click the Terminal icon to start the program. Step 2. On the menu bar, select Settings/Terminal Emulation. a. In the dialog box, click DEC VT-100 (ANSI). b. Click “OK”. BE1-BPR Appendix...
  • Page 139 Adjust the Baud Rate setting so that it matches the setting of the relay. default baud rate of the BE1-BPR is 9600. rate of the relay is 9600. Set the Data Bits at 8 .
  • Page 140: Appendix B • Commands Summary

    Read/Program date/time format PDIAG[=<DIAG1 mask>, <DIAG2 mask>] Read/Program diagnostic alarms as ON(1) or OFF(0) PDISPLAY[=<default_menu>,<default_screen>] Read/Program the default display screen PHOLD [ = <#####>] Read/program the 200 msec output hold mask PTARGET[= <iiiiiii>, <ooooo>] Read/Program the target data format BE1-BPR Commands Summary...
  • Page 141 Reads/changes a recloser (79) timer delay setting TEST Read diagnostic data TIME [= <hr>:<mn><f><sc>.<msc>] Read/change the time TLOG[#] Read Timer log TRIGGER[=<logic term>/Y] Read/Change Trigger logic or trigger a fault record. Read Model, SN, PN and Program data BE1-BPR Commands Summary...
  • Page 142: Appendix C • Relay Settings Record

    APPENDIX C • RELAY SETTINGS RECORD INTRODUCTION This appendix provides a complete listing of all BE1-BPR settings. This listing is in the form of a settings record that you may use to record information relative to your protection system. These settings sheets may be removed and photocopied.
  • Page 143 SETTINGS RECORD FOR BE1-BPR Substation ID Relay ID Date Page BE1-BPR Part Number Serial Number Version Number The following settings require global access (PW1). SECURITY SETTINGS Global PW and Access Ports = Password, 8 Char , Ports, F,R,B Protection Functions...
  • Page 144 REAR COM PORT ADDRESS SETTINGS Rear RS232/RS485 Port Address = ID,0=disabled,1-254 The following settings require protection access (PW1, PW2). PROTECTION SETTINGS Fault Detectors = Pick Up, Sec A , Moving Avg. Filter Window Time, Cycles Timers = Time Delay, mSec BE1-BPR Appendix...
  • Page 145 Fault Recording Settings Targets = IN, 0,1 Mask xxxxxxx , OUT, 0,1 Mask xxxxx PTARGET Oscillography Trigger = Logic Variable TRIGGER Alarm Settings Timer Log Settings = Timer Stop Logic , Type,L=under,H=over , Remaining Time Threshold, mSec. PTLOG1 BE1-BPR Appendix...
  • Page 146 Delta t, Current, msec BKRCON Breaker Status & Op Counter , Breaker Open Logic BKROPS Breaker Pre-insertion Resister = Reset Time, Min , Max Ops to Blk Reclose , Res Current V BKRRES SAVE SETTINGS; YES SAVE; Y BE1-BPR Appendix...
  • Page 147: Index

    Moving average filter ....2-3 COM Command ....4-43 BE1-BPR Index...
  • Page 148 I Command ..... 4-25 PDIAG Command ....4-27 BE1-BPR Index...

Table of Contents