Chapter 8: Regulations

Options affected by EN 50131 regulations

EN 50131 Grade 2

Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
1.2.6.n.3 Period, see "Transmitter polling interval requirements" on page 305.
2.2.1.n.3.3 View areas and 2.2.1.n.3.5 Control areas settings are identical
2.2.1.n.3.10 Buzzer silent, never
2.2.1.n.3.11 Quick set, off
2.2.1.n.3.12 Function keys, all set to None
2.2.1.n.3.17 ACK on keypad, set to None for non-LCD keypads
3.1.n.7.3 SMS control, disabled for all users
3.2.n.6 User group options, 25. No OP/CL reports option set to No
4.1.n.6.1 Inhibit, set to No for all zones with type 5. Panic, 6. 24H
4.1.n.6.6 Swinger shunt, set to Yes for all zones
4.1.n.6.26 ACK on keypad, set to None for all zones with type 9. Keyswitch
4.2.n.3 Entry time, 45 s maximum
4.2.n.5.1 Entry alarms, Instant
7.2.n.2 Active, set to No for all schedules.
8.1.2.1 Activation, external siren 90 to 900 s
8.1.2.2 Delay time, external siren 600 s maximum
8.1.3.1 Armed display, 30 s maximum
8.1.3.4 Mains reporting delay, 3600 s maximum
8.2.1 User code required, enabled
8.3.1 Armed display, always
8.3.3 Alarm list, disabled
8.4.1 RTS options, all enabled except zone technical alarm, which is optional
8.4.2 Inhibit includes, all allowed except engineer reset, which must be
disabled
8.4.6 Pending alarms, enabled
8.6.4 Swinger shunt ≥ 3
8.6.5 Report restore, on ACK
8.7.8.1 Remote config, No
9.3.n.2 Line fault, enabled per path used
9.3.n.3 Line fault delay, 0 s
It is required to apply the following supervision settings for wireless DGPs:
Short supervision: 20 minutes
Long supervision: 2 hours
Smoke supervision: 4 hours