Chapter 8: Regulations
Options affected by EN 50131 regulations
EN 50131 Grade 2
Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
•
1.2.6.n.3 Period, see "Transmitter polling interval requirements" on page 305.
•
2.2.1.n.3.3 View areas and 2.2.1.n.3.5 Control areas settings are identical
•
2.2.1.n.3.10 Buzzer silent, never
•
2.2.1.n.3.11 Quick set, off
•
2.2.1.n.3.12 Function keys, all set to None
•
2.2.1.n.3.17 ACK on keypad, set to None for non-LCD keypads
•
3.1.n.7.3 SMS control, disabled for all users
•
3.2.n.6 User group options, 25. No OP/CL reports option set to No
•
4.1.n.6.1 Inhibit, set to No for all zones with type 5. Panic, 6. 24H
•
4.1.n.6.6 Swinger shunt, set to Yes for all zones
•
4.1.n.6.26 ACK on keypad, set to None for all zones with type 9. Keyswitch
•
4.2.n.3 Entry time, 45 s maximum
•
4.2.n.5.1 Entry alarms, Instant
•
7.2.n.2 Active, set to No for all schedules.
•
8.1.2.1 Activation, external siren 90 to 900 s
•
8.1.2.2 Delay time, external siren 600 s maximum
•
8.1.3.1 Armed display, 30 s maximum
•
8.1.3.4 Mains reporting delay, 3600 s maximum
•
8.2.1 User code required, enabled
•
8.3.1 Armed display, always
•
8.3.3 Alarm list, disabled
•
8.4.1 RTS options, all enabled except zone technical alarm, which is optional
•
8.4.2 Inhibit includes, all allowed except engineer reset, which must be
disabled
•
8.4.6 Pending alarms, enabled
•
8.6.4 Swinger shunt ≥ 3
•
8.6.5 Report restore, on ACK
•
8.7.8.1 Remote config, No
•
9.3.n.2 Line fault, enabled per path used
•
9.3.n.3 Line fault delay, 0 s
It is required to apply the following supervision settings for wireless DGPs:
•
Short supervision: 20 minutes
•
Long supervision: 2 hours
•
Smoke supervision: 4 hours
302
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual