The decorative panel, controller, and branch piping are optional accessories and are not included with the
indoor unit. If necessary, please contact your contractor.
2. Do not insert or leave any foreign objects inside the indoor unit and verify that no foreign objects
remain inside in the indoor unit before the installation and Test Run. Failure to do this can result in
equipment failure and damage to the unit.
3. Necessary Tools and Instrument List for Installation
No.
1
Handsaw
2
Philips Screwdriver
3
Vacuum Pump
4
Refrigerant Gas Hose
5
Megohmmeter
6
Copper Pipe Bender
7
Manual Water Pump
8
Copper Tube Cutter
9
Brazing Kit
10
Hexagonal Wrench
4.

Installation Location

1. Install the indoor unit at a proper distance from the
walls as shown at right.
2. Install the indoor unit with sufficient space around it for operation and maintenance access as shown below.
Do not leave combustible materials inside the service space of the indoor unit.
Min.
19-11/16
(500)
Piping Connection
8
NOTICE
Tool
No.
11
12
13
14
15
16
17
18
19
20
Min.
Min.
19-11/16
19-11/16
(500)
(500)
Piping Connection
Tool
Wrench
Charging Cylinder
Manifold Gauge
Wire Cutter
Gas Leak Detector
Level
Clamp for Solderless Terminals
Hoist (for Indoor Unit)
Ammeter
Voltage Meter
Min. 59-1/16 (1500)
Piping
Connection
Side
Min. 59-1/16 (1500)
Min.
118-1/8
(3000)
Piping Connection
Service Sapce
NOTE:
Use tools and measuring
instruments (vacuum pump, gas
hose, charging cylinder, and
manifold gauge) exclusively for
the refrigerant R410A.
Unit: inch (mm)
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
Distance from Wall Side
Unit: inch (mm)
Min.
19-11/16
(500)
Min.
94-1/2
(2400)
P5417054