● The RUN indicator on the wired controller for the indoor unit will flash orange (0.5 second ON/ 0.5
second OFF), indicative of a fault or error having been generated with activation of protection devices
during the Test Run phase. Alarm code, unit model code, and the number of interconnected indoor
units will be displayed on the LCD as shown below. If the RUN indicator on the wired controller
flashes for two seconds ON and two seconds OFF, the source of the problem could be a failure in the
communication cable between the indoor unit and the wired controller (a loose or severed connection).
In this case, verify Section 9.3 "Alarm Code" and perform the appropriate troubleshooting measures.
Consult with an authorized service engineer if the problem cannot be resolved at your end.
Alarm Code:
MODEL : F .02
I.U.
IDU
ODU
O.U.
Sel.
40
01-02
22
Chek
AlarmRst
: RCI-3.0FSN3
: ******
Address
: ******
: RAS-3HVRNM2
OP MODE
Entr
OK
Refrigerant Cycle No.
of Indoor Unit Having
Trouble
01 - 02
22
Alarm Code:
MODEL : F . 02
Unit Model Code
Unit Model Code
The relationship between the unit model code
and the unit model is shown in the table below.
Indication
F
E
Indoor Unit No. of Indoor Unit
Having Trouble
Alarm Code No.
Total No. of Indoor Units in the
Same Refrigerant Cycle as the
Indoor Unit Having Trouble
Unit Model
VRF System
Except Above Models
P5417054