Clearances & Installation
Ensure that the mouth of the flame is positioned a minimum of 1500mm [59.1in] away from curtains,
flammable materials, and other sources of ignition. Be aware of drafts. The floor must be level and the Burner
positioned on a flat surface. The Burner must only be placed into non-combustible materials and must be
installed in accordance with the outlined safety requirements and clearances. Please send drawings to your
local representative to confirm the setting complies with the manufacturer's requirements prior to installation.
Burner Clearances
ecoSmart fire Burners can be installed into two (2) types of settings:
A. those that are encased by non-combustible materials similar to that
which you would find in a traditional masonry set-up. We refer to this
installation type as "WITHIN A fireBoX"
A. FIREBOX MEASUREMENTS FOR "WITHIN A FIREBOX" INSTALLATION (Fig.1)
minimum firebox
Burners
width (x)
BK SerieS
650mm [25.6in]
XL1200
1500mm [59.1in]
XL900
1200mm [47.2in]
XL700
1000mm [39.4in]
XL500
800mm [31.5in]
XS340
450mm [17.7in]
AB8
650mm [25.6in]
AB3
400mm [15.7in]
*We recommend centering the burner within the firebox (front and back, left and right).
If you choose to offset the burner placement, please follow the minimum distances
shown on Table AA. distances are measured from the outer edge of the burner flange.
AA. BURNER PLACEMENT "WITHIN A FIREBOX" (Fig.2)
minimum distance
Burners
to front (a)
BK SerieS
45mm [1.8in]
XL SerieS
50mm [2.0in]
XS340
45mm [1.8in]
AB SerieS
45mm [1.8in]
Custom made fireboxes must:
- Be made out of a non-combustible material such as stainless steel
- Be constructed to accommodate a top tray
- have built-in spacers of 20mm (0.8 in.) on all sides to ensure that it does not sit directly
against any combustible material and an air gap is incorporated for insulation around the
box construction. (Fig. 3)
The Fire Company Pty Ltd recommends using the Burner in a firebox manufactured by
The Fire Company Pty Ltd only. The Fire Company Pty Ltd is not liable for any injuries or
damages sustained through the use of custom made or privately commissioned fireboxes.
VB BURNER
the VB2 burner is specially designed as a 'drop-in' burner system to a purpose-built, existing
or new, fireplace setting. You should seek confirmation from the insert manufacturer and install
the fireplace according to the manufacturers instructions before inserting the burner.
www.ecosmartfire.com
minimum firebox
depth (Z)
365mm [14.4in]
350mm [13.8in]
350mm [13.8in]
350mm [13.8in]
350mm [13.8in]
300mm [11.8in]
450mm [17.7in]
350mm [13.8in]
minimum distance
minimum distance
to rear (B)
to left (c)
30mm [1.2in]
150mm [5.9in]
40mm [1.6in]
150mm [5.9in]
65mm [2.6in]
150mm [5.9in]
30mm [1.2in]
150mm [5.9in]
B .those that are not encased by non-combustible materials and set
up in a more modern setting without sides or a top. We refer to this
installation type as "WITHOUT A fireBoX"
minimum firebox
height (y)
650mm [25.6in]
500mm [19.7in]
500mm [19.7in]
500mm [19.7in]
500mm [19.7in]
450mm [17.7in]
800mm [31.5in]
Fig.1
500mm [19.7in]
minimum distance
to right (d)
150mm [5.9in]
150mm [5.9in]
150mm [5.9in]
150mm [5.9in]
Fig.2
Fig. 3
e-NRG Bioethanol is the only fuel to use in this appliance.