S E C T I O N 3 - System Wiring And Hookup; System Wiring Diagram - FBII XL-2T Installation And Setup Manual

Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

System Wiring Diagram

XL-2T
W A R N I N G
:
To prevent risk from
electrical shock, de-
NOTES:
1. Connect to a grounded metal water pipe (16ga. at 15 ft.).
energize the system
2. Total AUX. power available (including keypad power) is 500mA max. (180mA for fire installations).
control unit and
disconnect the
3. System must be tested on a weekly basis. For information, refer to manual.
telephone lines
4. Do not connect the transformer to a switch-controlled receptacle. Power varies with transformer (SEE NOTE 2).
before servicing
5. Installation of equipment and wiring methods are required to be in accordance with the National Electrical code
this unit.
6. Maximum of 4 keypads of LED type or LCD type.
7. Limited energy cable must be used.
1
8. Maximum for UL installations: Entry Delay, 45 sec.; Exit Delay, 60 sec.
ZONE 1
2.2k
2
9. For connection of VS-299 Siren Driver. Constant positive (+) unregulated output.
2.2k
ZONE 2
10. Programmable trigger outputs. If used for smoke detector power reset see Detail A.
3
4
11. 24 hr battery standby is required for fire installations. 4 hr battery standby is
ZONE 3
2.2k
5
12. System must be checked by a qualified technician once every three years.
2.2k
ZONE 4
6
13. Question 14, Location 1 must be set to ''00" for smoke detector power.
7
ZONE 5
2.2k
8
12VDC Reg., 500mA max.
2.2k
ZONE 6
9
2.2k
10
11
EARTH GND.
(SEE NOTE 1)
KEYPAD
(SEE NOTE 6)
SYSTEM STABILIZATION MODE: Upon power-up of the system and after completion of system program-
ming, all the lights on the LED keypads will flash momentarily and the LCD keypads will display
STANDBY! momentarily. EACH KEYPAD DISPLAY WILL THEN RETURN TO NORMAL. HOWEVER,
IF THE SYSTEM IS ARMED, THE ZONES WILL NOT RESPOND TO ALARM CONDITIONS FOR
APPROXIMATELY TWO MINUTES. The 2-minute interval is used to allow motion detectors (interior
zones) to stabilize on power-up in order to prevent false alarms. THE 2-MINUTE RESPONSE TIME CAN
BE DISABLED BY SIMPLY ENTERING A VALID USER CODE that disarms the system and reduces the
power-up reset time to approximately 5 SECONDS.
NOTE: If total system power is lost, then upon power restoral, the system will return to the previously
armed state.
System Wiring and Hookup
SYSTEM DEFAULT
JP1
RESET JUMPERS
Used for connection of devices rated from 11.5 to 13.1VDC. All circuits are power limited.
and ANSI/NFPA No. 72, Chapter 2.
See manual for programming information. Use model XL-2GTC trigger cable.
required for emergency/burglary.
AUX POWER
SMOKE DETECTOR POWER
(9.1-12.6VDC,
DC POWER (+)
(SEE NOTE 2)
50mA max.)
10-15.5VDC
+
(SEE NOTE 9)
+
12 13 14 15 16 17 18
19 20 21 22 23 24
FIRE & BURGLARY
M O D E L 3 6 8 C O R D
(11.5-13.1VDC, 1A max.)
TO RJ31X OR
CA31A JACK
HOME
TELCO
C O N N E C T I O N S F O R H O U S E H O L D F I R E / B U R G L A R A L A R M S Y S T E M
To re-load factory default values, remove all power
JP2
(AC & DC). Short JP1 to JP2. With short still applied,
re-apply power (AC then DC), wait 5 seconds, then
remove short with power still applied.
F 3
F 2
AUX
F 1
BELL
TRIGGER OUTPUTS
(SEE NOTE 10)
25
P1
TRANSFORMER
ALARM OUTPUT
12VAC, 20VA
(Connect to 24 HR.
650mA UL
120VAC, 60 Hz Outlet
INSTALLATION
SEE NOTE 4)
+
-
BELL
+
-
+
SPEAKER
S E C T I O N
( P E R U L S T A N D A R D S U L 9 8 5 A N D U L 1 0 2 3 )
CONTROL PANEL
POWER
21 16
1
2
BAT
MODEL ESL2048
+
EOL RELAY
4A
BATT
1A
_
BAT
3A
UL INSTALLTIONS REQUIRE LISTED
END-OF-LINE DEVICE. USE RESISTOR
FROM EOL22 KIT. LOOK FOR LISTING
MARK ON ITEM.
W A R N I N G :
NOTE: UL VERSIONS
CONTAIN PTC's IN
THIS UNIT INCLUDES AN ALARM
PLACE OF FUSES
VERIFICATION FEATURE THAT WILL
RESULT IN A DELAY OF THE SYSTEM
ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL
UNIT PLUS SMOKE DETECTOR) SHALL
NOT EXCEED 60 SECONDS. NO OTHER
INITIATING DEVICES SHALL BE CON-
NECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY
12V, 4-6AH
HAVING JURISDICTION.
BATTERY
MODEL 1240A
CIRCUIT
CONTROL UNIT
(SEE NOTE 11)
(ZONE)
DELAY-SEC
_______
_____20______
PRODUCT COVERED UNDER
US PATENT #4,791,658
3
D E T A I L A
SMOKE DETECTOR
9.5 - 12.2VDC
ZONE
LISTED
HOUSEHOLD
3
4
THERMOSTAT
ESL104
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
2.2k EOL RESISTOR
SMOKE DETECTOR
MODEL DELAY-SEC
______ __________
3–1