XL-2T Installation & Setup Guide
24-Hr. Zones
FIRE - Fire with Verification zones contain Fire Verification Logic. Upon detection of the first
violation, smoke detector power on conventional 4-wire smoke detectors connected to ZONE
modules will be reset for a period of 8 seconds. After this time period, power is restored. For a
period of 5 seconds, the fire zone will not be scanned, allowing the smoke detectors to settle.
Future violations within a two-minute period will result in a PULSING BELL OUTPUT,
RAPID PULSING ZONE LED, and IMMEDIATE transmission to the CS. Fire signals cannot
be aborted.
Entry of any valid user code will silence the sounder and bell. Entry of a valid user code for a
second time will reset smoke detector power and clear alarm memory. If the system detects
that the fire zone is still violated within 2 minutes of power reset, the zone LED will pulse
slowly to indicate a fire trouble. Thereafter, smoke detector power will be reset every 4 min-
utes automatically in an attempt to clear the fire zone.
In the event the fire zone experiences an open, the system indicates fire trouble by pulsing the
keypad zone LED and sounder slowly. The system trouble code (followed by the zone code) is
reported to the CS.
Fire without Verification zones do not follow verification. They will trip instantaneously upon
a violation.
Fire zones will also cause a TROUBLE condition if the bell or speaker is disconnected.
Any valid user number silences the keypad. When a zone is selected for fire, it will go into a
trouble condition whenever the bell or speaker is disconnected.
24-HR. ALARM - This zone type is always active, independent of the system arming status.
Programming options include audible (STEADY BELL) or silent (NO BELL or keypad indica-
tions), with or without restore codes. Upon violation, the zone LEDs will pulse rapidly (audi-
ble zones only) and an immediate CS transmission will occur that cannot be aborted.
24-Hour Alarm zones can be bypassed; however, they cannot be unbypassed if a violation ex-
ists on the zone terminals.
NOTE: 24-Hour zones should not be used for perimeter protection.
24-HR. TROUBLE - This zone type is always active, independent of the system arming status.
Programming options include audible (PULSING KEYPAD SOUNDER) or silent, with or
without restore codes. Upon violation, the zone LED will pulse slowly. TROUBLE condition
must exist for 15 seconds before a transmission will occur. The keypad display and sounder
will clear upon zone restoral.
Fire zones cannot be bypassed. 24-HOUR TROUBLE must NOT be used for fire/burglary
protection.
24-Hour Trouble zones can be bypassed; however, they cannot be unbypassed if a violation
exists on the zone terminals. Any valid user code silences the keypad.
KEYSWITCH - Keyswitch zones toggle the arming status of the system. A keyswitch auto-
matically arms the system in the STAY mode if the keyswitch is held for three seconds or
more; it arms in AWAY mode if held for 2 seconds or less.
Keyswitch zone operation has NOT been tested by Underwriters Laboratories.
6–22