7 Detailed function specification
F18.12 Timing run stop time
When F18.11 Timing operation function enabled, the driver will start the timer
with inverter start.
The drive will stop automatically and the multi-function Yi (Set Yi as the 33
function) will output an indicator signal when reach to the set stop time.
The timer of inverter start form 0 every times, the user can
monitor the current operation time through the F0 Group.
Note
F18.13 Currently run arrival time
When the actual operation time reach to this time, the multi-function Yi (choose
Yi as 34 function) will output an indicator signal of "Currently operation time
reached".
Keyboard UP/DOWN selection
F18.14
under monitor mode
0: Keyboard frequency provision frequency adjusting
1: PID digital reference value adjusting
2~6:Reserved
When F18.14 =1, UP/DOWN is used to adjust the PID digital reference value in
Monitor Mode merely.
When F18.14 =0, UP/DOWN is used to adjust the frequency value not only in
Monitor Mode when choose frequency digital reference channel.
V/F vibration restrain end
F18.15
frequency
In V/F Control mode, when the output frequency of inverter is bigger than the
limit frequency,the suppression of F03.12 will be disabled. Adjusting F18.15 can
restrain the shake phenomenon of motor in a large range.
Torque closed loop control
F18.16
selection
When F18.16=0,torque open loop control is available
When F18.16=1,torque close loop control is available, which can increase the
precision of torque control
F18.17
Reserved
~
F18.24
194
Range: 0.1~6500.0Min
Range: 0.0~6500.0Min
Range: 0~6
Range: 0.00Hz~upper
limit frequency
Range: 0,1(when
F00.24=1 or 2)
2.0Min
1.0Min
0
50.00Hz
1