Eliminate Fault; Status Indicator On The Individual Installed Or Higher-Level Cascade Module; Status Indicator On The Lower-Level Cascade Module; Environment / Disposal - Bosch MC 400 Installation Instructions For Skilled Labour

Ems 2/ems plus/ems
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
5

Eliminate fault

Only use original spare parts. Any damage resulting from
spare parts that are not supplied by the manufacturer is
excluded from liability.
If a fault cannot be rectified, please contact the responsible
service engineer.
The indicator shows the operating condition of the module.
4 5 6
3
7
2
1
0
10
5.1
Status indicator on the individual installed or higher-
level cascade module
Operating
Icon
Possible cause
Remedy
Constantly
Power supply
▶ Turn on the mains power supply.
OFF
interrupted.
Fuse faulty.
▶ When the power supply is switched
Short circuit in BUS
▶ Check BUS connection and repair if
connection.
Constantly
Coding card in invalid
▶ Set the coding card.
red
position or in
intermediate position.
Temperature sensor is
▶ Check temperature sensor.
defective
▶ If values do not match, replace the
▶ Check voltage at temperature sensor
▶ If the sensor values match but the
Internal fault
▶ Replace module.
Flashing
Stop switch on I3 is
▶ Check the stop switch.
red
open
Flashing
Switch for max.
Check max switch on I2
green
performance is closed
Flashing
Initialisation
yellow
Constantly
Coding card set to 0
▶ Set the coding card.
green
No fault
Normal operation
Table 7
MC 400
8
9
6 720 647 922-52.1O
off, replace the fuse (
fig. 21,
page 89)
required.
sensor
terminals in the module.
voltage values do not match, replace
the module.
5.2

Status indicator on the lower-level cascade module

Indicator
light
Possible cause
Remedy
Constantly
Power supply
▶ Switch on the power supply.
OFF
interrupted.
Fuse faulty.
▶ When the power supply is switched
Short circuit in BUS
▶ Check BUS connection and repair if
connection.
Constantly
Coding card in invalid
▶ Set the coding card.
red
position or in
intermediate position.
Internal fault.
▶ Replace module.
Flashing
Initialisation
yellow
Constantly
Coding card set to 0.
▶ Set the coding card.
green
No fault
Normal mode
Table 8
6

Environment / disposal

Environmental protection is a fundamental corporate strategy of the
Bosch Group.
The quality of our products, their efficiency and environmental safety
are all of equal importance to us and all environmental protection
legislation and regulations are strictly observed.
We use the best possible technology and materials for protecting the
environment taking into account economic considerations.
Packaging
We participate in the recycling programmes of the countries in which our
products are sold to ensure optimum recycling.
All of our packaging materials are environmentally friendly and can be
recycled.
Old electrical and electronic appliances
Electrical or electronic devices that are no longer
serviceable must be collected separately and sent for
environmentally compatible recycling (in accordance
with the European Waste Electrical and Electronic
Equipment Directive).
To dispose of old electrical or electronic devices, you
should use the return and collection systems put in place
in the country concerned.
Eliminate fault | 19
off, replace the fuse (
fig. 21,
page 89)
required.
6 720 819 669 (2016/05)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents