Initial Programming Menu
Programs
A maximum of (8) programs are available.
Each program has a maximum of (8) process set points.
The program and process set point in use is displayed as P(1-8) S#(1-8).
Programs utilize global settings.
Global Settings
Multiple programmable menu settings common to all programs (global)
to speed programming and insure consistent heater operation, program
to program.

Process Menu

Process Set Point
A maximum of (8) Process Set Points are available with a temperature
range of 60°F (15°C) to 240°F (115°C).
The Process Set Point is displayed as "SP."
Process Set Points not being used can be turned to an "Off" setting.
Process Times
Any of the (8) Processes can be timed. Each timed Process has a range of
00:00:01 to 23:59:59. The conclusion of a timed Process will immediately
proceed into the next Process. If the last Process of the program is timed, it
will proceed to the selected start position (see Looping Mode, page 7) after
timing out. The letter "T" will be displayed indicating a timed Process. Press
the up or down arrows on the TDM02 to scroll between the screens show-
ing the Process Set Point and the sensed temperature AND the sensed
temperature with the time remaining in the Process (hh:mm:ss).

Operation Menu

Soft Start (Global Setting)
The Soft Start feature controls the initial rate of voltage change to the mod-
ulator. Soft Start operates when switching from a lower Process tempera-
ture to a higher Process temperature. It is designed to slow the initial input
rate to the burner. This feature is available in three settings: slow, medium,
and fast and may be turned off. "Ss" (slow), "Sm" (medium) or "Sf" (fast)
is displayed during the time the Soft Start is active. This feature is compre-
hensive to all Set Points.
Max Valve VDC (Global Setting)
This feature limits the maximum voltage applied to the modulator. It has a set-
ting range of 7 to 25 VDC. This feature is comprehensive to all Set Points.
© 2006 Maxitrol Company, All Rights Reserved
(TM02 required)
4