User's / Programming Guide
���
www.maxitrol.com
© 2006 Maxitrol Company, All Rights Reserved

Advertisement

Table of Contents
loading

Summary of Contents for Maxitrol Selectra MP2+

  • Page 1 Multiple Program Process Temperature Controller User’s / Programming Guide ��� www.maxitrol.com © 2006 Maxitrol Company, All Rights Reserved...
  • Page 2: Warnings

    This control must be electrically wired in accordance with lo- cal codes, or in the absence of local codes, with the Nation- al Electrical code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1 as applicable. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 3: Table Of Contents

    Operation Menu ................13 Diagnostic Menu ................15 Operation ....................16 MP2+ Multiple Program Process ............16 MP2+ Multiple Program w/ TM02 Multifunctional Timer Control .... 17 Wiring Diagram ..................18 Glossary ....................19 © 2006 Maxitrol Company, All Rights Reserved...
  • Page 4: Features

    Max Valve VDC (Global Setting) This feature limits the maximum voltage applied to the modulator. It has a set- ting range of 7 to 25 VDC. This feature is comprehensive to all Set Points. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 5 Set Point to another. It is available for each Process. The Ramping Rate determines the amount of temperature change per hour in one-min- ute steps. It has a range of 60 Deg/hr to 900 Deg/hr. The change can be positive or negative. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 6: Diagnostic Menu

    This feature limits the maximum temperature for each Process. It has a range of 60°F (15°C) to 240°F (115°C). It does not allow the Process Set Point to be set in excess of the Maximum Process Temperature setting. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 7 After last manual process of a program or after last timed process of a program expires, the controller defaults to the first process of the same program. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 8: Other Features

    The following voltage will be measured across the #9 terminals: Note Polarity Controller in the “READY” position 0 VDC Controller operating in any of the 8 processes making up a Program 24 VDC 2W max © 2006 Maxitrol Company, All Rights Reserved...
  • Page 9: Technical Data

    1,000 ohm RTD TS194Q use with mixing tube Valves M411, M511, M611, MR212 NOTE: Please read safety warning instructions fully for Maxitrol Modulator Valves [MI2040] prior to attempting to install, operate, and/or main- tain the MP2+ system. Components AM02+ Amplifier ...
  • Page 10: Menus

    60°F(15°C) to 240°F(115°C) Min Proc Temp  60°F(15°C) to 240°F(115°C) Calibration  Calibration Process #(1 - 8)  -10°F(-5.6°C) to +10°F(5.6°C) Monitor  On, Off Looping Mode  Ready, First Process F/C Mode Software Version © 2006 Maxitrol Company, All Rights Reserved...
  • Page 11: Programming The Mp2+ System

    Press twice or hold for 10 seconds to  abort a timed process. Screen Indicators **STORED** will appear on the screen to confirm entry accepted.  T indicates a timed process.  M indicates a manual process.  © 2006 Maxitrol Company, All Rights Reserved...
  • Page 12: Initial Menu

    Repeat steps 1 through 4 for Set Points #(2 - 8). NOTE: Process #1 CAN NOT be OFF. For unused Process Temperature Set Points, press down arrow until “Off” is displayed. Set Points #(2 - 8) are factory set to “Off.” © 2006 Maxitrol Company, All Rights Reserved...
  • Page 13: Operation Menu

    2 Max Ramp VDC, set voltage value (5 V to 24 V), press 3 **Stored** will flash 4 times to confirm entry. NOTE: Voltage can not be set greater than Max Valve VDC. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 14 XXX Hours Clear hours Are You Sure? scroll for Y or N, press If Y, Timer1 Hrs Clear flashes to confirm entry. Set alarm hours T1 Proc # Alarm, scroll to set hrs, press © 2006 Maxitrol Company, All Rights Reserved...
  • Page 15: Diagnostic Menu

    Set Point #, press 3 Cal Proc # set Temp. value (-10°F (-5.6°C) to 10°F (5.6°C)), press **Stored** will flash 4 times to confirm entry. Repeat steps 1 through 4 for Set Points #(2 - 8). © 2006 Maxitrol Company, All Rights Reserved...
  • Page 16: Operation

    Process. Pushing and releasing Button 1 or momentary latching of TB1 during the last Process of a program will cause the MP2+ System to return to Process 1. Multiple contacts used to switch Processes are to be wired in parallel. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 17: Mp2+ Multiple Program W/ Tm02 Multifunctional Timer Control

    Relay (1 - 8), on the TM02. The Program indicator uses a corresponding terminal labeled Relay 9. Wire each indicator (LED, relay coil, etc.) 24 VDC 2 W maximum directly to the desired corresponding terminal. See figure A, page 18. Note polarity where applicable. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 18: Wiring Diagram

    Wiring Diagram Fig. A Wiring Diagram...
  • Page 19: Glossary

    “Ready” Screen display. When selected, it appears prior to the start of a program involving timed processes. A momentary switch closure moves the con- troller from the “Ready” position to the First Process. © 2006 Maxitrol Company, All Rights Reserved...
  • Page 20 © 2006 Maxitrol Company, All Rights Reserved 23555 Telegraph Road Southfield, MI 48033 248.356.1400 tel 248.356.0829 fax www.maxitrol.com...