Operation Menu - Maxitrol Selectra MP2+ User & Programming Manual

Multiple program process temperature controller
Hide thumbs Also See for Selectra MP2+:
Table of Contents

Advertisement

Process Times
Scroll
1
Each Process can be either Timed or Manual.
2 Time Process #, scroll
MANUAL will be the default.
3 Scroll
Set Seconds, Minutes or Hours value with
a
press
ENT
**Stored** will flash 4 times to confirm entry.
b
c
Repeat steps 3 through 3b for each time segment.
for Manual (untimed) Processes
d
Default setting or when programmed to 00:00:00.
Repeat steps 1 through 3 for Set Points #(2 - 8).

Operation Menu

Soft Start (Global Setting)
1
Scroll
2 Soft Start, scroll
3 **Stored** will flash 4 times to confirm entry.
Max Valve VDC (Global Setting)
1
Scroll
Max Valve VDC, set
2
**Stored** will flash 4 times to confirm entry.
3
Max Ramp VDC
1 Scroll
2 Max Ramp VDC, set
3 **Stored** will flash 4 times to confirm entry.
NOTE: Voltage can not be set greater than Max Valve VDC.
© 2006 Maxitrol Company, All Rights Reserved
(TM02 required)
to Times and press
to Seconds, Minutes or Hours, press
.
programming:
to Soft Start and press
to Off, Slow, Medium or Fast, press
to Max Valve VDC, press
voltage value (7 V to 25 V), press
to Max Ramp VDC, press
voltage value (5 V to 24 V), press
13
Programming the MP2+
.
ENT
to Set Point #, press
.
ENT
.
ENT
.
ENT
.
ENT
.
ENT
,
.
ENT
.
ENT
.
ENT