Total Bandwidth (Global Setting)
1
Scroll
2 Total Bandwidth, set
to 15°F (8.3°C)), press
3 **Stored** will flash 4 times to confirm entry.
Offset
1 Scroll
2 Offset Temp Process #, scroll
3 Offset Temp Process #, set
10°F (5.6°C)), press
**Stored** will flash 4 times to confirm entry.
4
Repeat steps 1 through 4 for Set Points #(2 - 8).
5
Ramping
1
Scroll
2 Ramping Process #, scroll
Rmp Rate Proc #, set
3
press
.
ENT
4
**Stored** will flash 4 times to confirm entry.
5
Repeat steps 1 through 4 for Set Points #(2 - 8).
Timers
(TM02 required)
Scroll
1
2 Timer Process #, scroll
3 Timer Process #, scroll
Timer 1: T1 Proc #, scroll
4
or Set Alarm Hours, press
View hours
a
Clear hours
b
c
Set alarm hours
d
© 2006 Maxitrol Company, All Rights Reserved
to Total Bandwidth, press
Bandwidth (5°F (-2.8°C)
.
ENT
to Offset Temp, press
.
ENT
to Ramping, press
to Timers, press
XXX Hours
Are You Sure? scroll
If Y, Timer1 Hrs Clear flashes to confirm entry.
T1 Proc # Alarm, scroll
Programming the MP2+
.
ENT
.
ENT
to Set Point #, press
Offset (-10°F (-5.6°C) to
.
ENT
to Set Point #, press
Ramp Rate (Off, 60 to 900 Deg/Hr),
.
ENT
to Set Point #, press
to Timer 1 or Timer 2, press
to View Hours, Clear Hours
.
ENT
for Y or N, press
to set hrs, press
14
.
ENT
.
ENT
.
ENT
.
ENT
.
ENT
.
ENT