Emerson 1410H Reference Manual page 50

And 781 field links
Hide thumbs Also See for 1410H:
Table of Contents

Advertisement

Appendix B
February 2019
Special Conditions for Safe Use (X):
1.When installed as Division 2 equipment, the Model 1410 Smart Wireless Gateway shall
be mounted within a tool-secured enclosure which meets the requirements of ANSI/ISA
61010-1 and be capable of accepting the applicable wiring methods per the NEC.
Canada
N6 Canada Division 2
Certificate 2646342 (CSA)
Standards CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 213-M1987 (R2013), CSA C22.2
Markings
Shall be powered by a class 2 power supply.
Suitable for dry indoor locations only.
Equipment must be installed in a suitable tool accessible enclosure subject to the end
use application.
Using the 1410H and the 781 Field Links in a hazardous location requires barriers
between the two units.
Europe
N1 ATEX Type n
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. The equipment must be installed in an area of not more than Pollution Degree 2 as
defined in IEC 60664-1, and in an enclosure that provides a degree of protection of at least
IP54 and meets the relevant requirements of EN 60079-0 and EN 60079-15.
2. External connections to the equipment must not be inserted or removed unless either
the area in which the equipment is installed is known to be non-hazardous, or the circuits
connected have been de-energised.
3. The equipment is not capable of withstanding the 500V electrical strength test as
defined in clause 6.5.1 of EN 60079-15: 2010. This must be taken into account during
installation.
4. When fitted, the surface resistivity of the remote antenna is greater than 1G. To avoid
electrostatic charge build up, it must not be rubbed with a dry cloth or cleaned with
solvents.
International
N7 IECEx Type n
Certificate
50
No. 61010-1 – 2012, ANSI/ISA-12.12.01 – 2012, UL61010-1, 3
Suitable for CL I, DIV 2, GP A, B, C, D; T4 (-40 °C ≤ Ta ≤ 70 °C)
Baseefa14ATEX0125X
EN 60079-0: 2012, EN 60079-15: 2010
II 3 G Ex nA IIC T4 Gc, T4(-40 °C ≤ Ta ≤ +75 °C), V
IECEx BAS 14.0067X
Reference Manual
00809-0500-4410
rd
Edition
= 30Vdc
MAX
Emerson.com/Rosemount