Viii.5.E. Opening Percentage Curve Of The Fee Module - Caladair EXAECO 10 Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

®
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
OPERATING AND COMMISSIONING INSTRUCTIONS
VIII.5.e.
Opening percentage curve of the FEE module
ouvert
In Standard the minimum% opening of the RMR and RMS registers is 30% or about
15% fresh air flow
100% opening of RMS fresh air and return air registers RMR =
output AO1 = 0V = all fresh air
fermé
0% opening of RMS fresh air and return air registers RMR =
output AO1 = 10V = all recycling
30% opening of RMS fresh air and return air registers RMR =
output AO1 = 7V = mixture
MS-CDF-002
Ind D
Maj. 02/11/2018
Créé par : JC
Validé par : AR
Page 45/49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Exaeco seriesExaeco 13Exaeco 17Exaeco 22

Table of Contents