OPERATING AND COMMISSIONING INSTRUCTIONS
Running mode
V.1.b. Temperature menu
Temperature.
(8)
Temperature setpoint setting (see chapter V.4.d)
MS-CDF-002
Input/Output
Extract Temperature
Real:
Setpoint : 21°C (8)
...
Outdoor temp :
Supply temp
Real :
Setpoint :
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
AO
(analogue outputs)
AO Ext1
(analogue outputs)
DO
(Digital output)
DO Ext1
(Digital output)
Cons
Créé par : JC
®
AO1: Y4 S-Suppl
(0V = recycling)
(10V = Fresh air)
...
AO1: Y1 Heating.
AO2: Y2 Exchang.
AO3: Y3 Cool
AO4: Ctrl SAF
AO5: Ctrl EAF
DO1: Reg. AN
DO2: Reg. Recy
DO3: Heat demand
DO4: Cool demand
DO1: V.freq SAF
DO2: V freq EAF
DO3: Rot exch. activ.
DO4: Heat Pump
DO5: Cool pump.
DO6: Surventil.activ
DO7: Somme alarme
Setpoint comp ext
-20°C = 25°C (8)
-15°C = 24°C (8)
-10°C = 23°C (8)
Consigne comp ext
-5°C = 23°C (8)
0°C = 22°C (8)
5°C = 20°C (8)
Setpoint comp ext
10°C = 18°C (8)
15°C = 18°C (8)
Validé par : AR