Caladair EXAECO 10 Operating And Commissioning Instructions page 34

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS
6
Filter guard 1
External frost
8
guard
High supply air
15
temp
Electric heating
23
is overheated
Sensor error
27
outdoor temp
Rotation sentinel
29
exchanger
Supply air fan
control error
31
Extract air fan
32
control error
35
Manual
... in Manual
36 à
44
mode
Internal battery
48
error
Sensor error
49
supply air temp
Sensor error
50
extract air temp
Sensor error
55
pressure VAS
MS-CDF-002
Ext DI1 must be
open « off » if there
C
is no default
Ext DI3 must be
closed « Fer »if
C
there is not default
Ext AI1 is mounted
A
higher than 50°C
Ext DI3 must be
closed « Fer » if
A
there is no default
Control the value
A
Ext AI2
Control the value
C
DI6
Difference higher
than 50Pa between
exhaust setpoint
C
and pressure on
Ext UAI1
Difference higher
than 50Pa between
exhaust setpoint
C
and pressure on
Ext UAI2
Runs in manual
C
mode
Functions are
modified in
C
manual mode
Error battery intern
A
Control the
A
Value on Ext AI1
Contrôler la
A
valeur sur Ext AI3
Control the value
A
on Ext UAI1
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
1.
Filters are dirty
2.
Filters pressure switches are wrongly connected
(Pressure switches must be set on 150 Pa for G4
5s
200Pa for F7).
8.
Control the connection of the crystal tubes (chapter
IV.6
1.
THA thermostat is not set on 5°C
2.
THA thermostat s disused
120s
3.
Circulating pump is disused
4.
3 ways valve 3 is wrongly connected, hydraulically
or is disused
1.
Exhaust temperature is higher than 50°C
2.
Temperature setting is too high
30s
3.
Exhaust fan is stopped (vent
AS Default) when hot battery is in full capacity.
1.
Safety thermostat THS is activated. To reset THS,
push on the rearmament on the electric battery
5s
2.
Power cut
3.
Exhaust fan is stopped (vent
AS Default) when electric battery is in full capacity
Outside temperature sensor SEG is disused .Outside
5s
temperature sensor SEG is wrongly connected (see chapter
IV.3)
300s
The belt of the exchanger is brocken
The network of blowing do not correspond to the fan or
30min
to the setpoint.
Filter is dirty
Return network do not correspond to the fan or to the
30min
setpoint.
Filter is dirty
Default à titre indicatif (le centrale est passée à l'arrêt en PV
5s
ou en GV directement sur l'afficheur (voir (7) chapitre V.3.a)
5s
In the Auto Manual menu everything must be in Auto.
Intern battery of the CORRIGO is disused
5s
Change the battery quickly in order to not loose programm.
See chapter VII.2
Outside temperature sensor SSG is disused
5s
Outside temperature sensor SSG is wrongly connected (see
chapter V.3.a)
Outside temperature sensor SRG is disused
5s
Outside temperature sensor SRG is wrongly connected (see
chapter V.3.a)
0-10V signal is inverted
5s
Pressure transmittor on fresh air is in short-circuit
Créé par : JC
®
Validé par : AR
Page 34/49