OPERATING AND COMMISSIONING INSTRUCTIONS
V.2. Operator parameters modification ( password 3333 required)

V.2.a. Dates and hours clocks setting

V.2.a.1.
Access : Hour Date setting
Date and hour of the regulator are set by defaut in the CORRIGO controller. Summer/Winter time is automatically managed.
V.2.a.2.
Access :
o
Timer normal speed : Time settings / normal speed program
o
Timer reduced speed : Time settings / slow speed program
o
Timer recirculation : Time settings / Timer 5
System is set to work in normal speed (HS-1/1) 07:00 - 22:00 in slow speed (LS-1/2) 22:00 - 06:00 except DIVA / LOBBY /
QUATTRO versions which work in slow speed (LS-1/2)
As indicated in arborescence you also have the possibility to modify Monday to Friday periods by pressing the right button
when you are on the Monday screen
Nota : if slow speed (LS-1/2) and normal speed (HS-1/1) are activated in the same time window, unit works in high speed
Operation exceptions:
o
o
(Example: If unit is in (LS-1/2) between 02:00 and 06:00 and in (HS-1/1) the rest of the time. Then NIGHT
COOLING is allowed to work only from 02:00 to 06:00 AM)
V.2.a.3.
Access : Time settings / Holidays
The system is set without vacation period. In case you wish to reduce the operating time during holiday periods, set the holiday
operating hours as described in chapter V.3.4), then set your holiday days.Modification de la vitesse / pression en PV et GV
V.2.a.4.
Access : ventilation Regul / Frequency control VAS 1/1 and 1/2 or frequency control VAR 1/1 et 1/2
You can modify the rotation speed of the unit in PV-1/2 (slow speed) and in HS-1/1 (normal speed) for each fan to set the
airflows.
o
To set the initial airflow (GV-1/1), force the system in normal speed with available terminals « Forced start HS »
(bridge between 41 and 42 terminals).
o
To set the initial airflow LS, force the system in slow speed with available terminals « Forced start LS » (bridge
between 39 and 40 terminals).
V.2.a.5.
Access : ventilation Regul / Pressure control VAS 1/2 or Pressure control VAR 1/2
You can modify the constant pressure of the unit for each fan to set the airflows.
o
To set the initial airflows LS, force the le system in normal speed with available terminals « Forced start LS » »
(bridge between 39 and 40 terminals).
V.2.a.6.
Access : ventilation Regul / Airflow control VAS 1/1 and 1/2 or Airflow control VAR 1/1 and 1/2
You can modify the rotation speed of the unit in PV-1/2 (slow speed) and in HS-1/1 (normal speed) for each fan to set the
airflows.
o
To set the initial airflow (GV-1/1), force the system in normal speed with available terminals « Forced start HS »
(bridge between 41 and 42 terminals).
o
To set the initial airflow LS, force the system in slow speed with available terminals « Forced start LS » (bridge
between 39 and 40 terminals).
MS-CDF-002
Date and hour of the CORRIGO controller [(1) chapter V.3.d]
Hour programmation of the functionning system [(2) (3) chapter V.3.d]
®
®
DIVA
/QUATTRO
: For CO2 regulation do not activate any normal speed time window (GV-1/1)
LOBBY: Only slow speed clock (LS-1/2) must be activated
NIGHT COOLING: Only works if unit is in slow speed (LS-1/1) between 00:00 and 07:00.AM
Holidays periods [(4) chapter V.3.d]
®
ECO / DIVA
/ [(5) chapitre V.3.c]
®
LOBBY
[(5) chapitre V.3.c]
MAC2
®
/QUATTRO
®
[(5) chapitre V.3.c]
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
Créé par : JC
®
Validé par : AR
Page 27/49