Vi.3. Acknowledge The Default « Timer Service - Caladair EXAECO 10 Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS
Sensor error
56
extract VAR
59
CO2 sensor error
... in manual
85
mode
86
Time for service
... in manual
87
mode
VI.3.
Acknowledge the default « timer service »
These settings require an access to the setting menu. You need the access rights to "service" level. Follow the instructions
below.
access rights
Enter the code 2222 with directional arrows then press the OK button. Press the left arrow twice to reach the menus. In case of
mistake press C button twice and start again.
Settings
An alarm occurs every 6 months to remind the maintenance visit. Enter YES to reset the counter to zero
MS-CDF-002
Control the value
A
on Ext UAI2
Control the
A
Value on Ext AI4
Functions are
modified in
A
manual mode
Regular visit
C
Functions are
modified in
C
manual mode
Enter
Quitter
Reset to zero
Filters counter
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
0-10V signal is inverted
5s
Pressure transmittor on intake air is short circuited
0-10V signal is inverted
5s
CO2 transmittor is in short-circuit
5s
In Manuel Auto menu everything must be in Auto.
5s
See chapter VI.3
5s
In Manuel Auto menu everything must be in Auto.
Enter password 2222
Of the required autoris. level:
Current level : SERVICE
filter alarm
Reset to zero of the
Timer : YES
Créé par : JC
®
Validé par : AR
Page 35/49