OPERATING AND COMMISSIONING INSTRUCTIONS

V.1.c. Ventilation menu

Ventilation
(5)
Speeds, pressures, airflows (see chapter V.4.b)
(6)
CO2 setpoint except DIVA and QUATTRO (voir chapitre V.4.c)
MS-CDF-002
Frequency control SAF
(STANDARD OU DIVA)
Output: 70 (5)
or
Pressure Control SAF
(LOBBY)
Real : 183Pa (example)
Setpoint : 180 Pa(5)
or
Air flow SAF
(MAC2 QUATTRO)
Real : 1503m3/h (example)
Setpoint : 1500m3/h(5)
Frequency control EAF
(STANDARD OU DIVA)
Output: 70 (5)
or
Pressure Control EAF
(LOBBY)
Real : 183Pa (example)
Setpoint : 180 Pa(5)
or
Air flow EAF
(MAC2 QUATTRO)
Real : 1503m3/h (example)
Setpoint : 1500m3/h(5)
CO2 (except DIVA
Réal : 654ppm (exemple)
Setpoint : 1000ppm (6)
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
%
%
OU QUATTRO
)
®
®
Créé par : JC
®
Frequency control SAF
Sp 1/1: 70% (5)
Sp 1/2: 50% (5)
...
Pressure Control SAF
Sp 1/1: non utilisé
Sp 1/2: 180Pa (5)
...
Air flow SAF
Sp 1/1: 5000m3/h (5)
Sp 1/2: 2500m3/h (5)
...
Pressure Control SAF
Sp 1/1: non utilisé
Sp 1/2: 180Pa (5)
...
Contrôle pression VAR
Cons 1/1: non utilisé
Cons 1/2: 180Pa (5)
...
Air flow SAF
Sp 1/1: 5000m3/h (5)
Sp 1/2: 2500m3/h (5)
...
Validé par : AR