OPERATING AND COMMISSIONING INSTRUCTIONS
Fonction
Alarm synthesis
SAF default
EAF default
Filter default
Antifreeze default
Fire default
Electric battery overheat
Outdoor temperature default
Battery default
Supply temperature default
Extract temperature Default
MS-CDF-002
INPUT STATUT REGISTER
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
If 1 = ALARM
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
Description
Créé par : JC
®
Exo
Modbus
Défaut
type
Adresse
value
L
10163
L
10033
L
10034
L
10038
L
10040
L
10042
L
10055
L
10059
L
10080
L
10090
L
10091
Validé par : AR
Page 48/49