OPERATING AND COMMISSIONING INSTRUCTIONS
VII.

MAINTENANCE

VII.1.
Mandatory maintenance
Outside the unit
Check the ducts, flexible sleeves, anti-vibrating plots; replace them if necessary. Check that all elements connected to the unit
do not give any vibration to the unit.
Unit and Regulation
Check connection every year
Filtration
Do not damage the filters
Classification
Max pressure drop
Gravimetric
Opacimetric
Componants
Filtration
Rotative exchanger (12 month)
Check belt and change it if necessary
VII.2.
Battery replacement
When low battery alarm starts and red LED is lighting, this indicates that the safety battery for the safeguard of the memory
and clock is too low. Follow the instructions below to change them. A condenser keeps the safeguard and let the clock running
for 10 minutes left after power cut. If the replacement of the battery takes less than 10 minutes, you will not have to reset the
program and clock will work normally.
Replacement battety is a CR2032 type
Press the clips on each sides of the box with a little screwdriver to open the the top of the box.
MS-CDF-002
Efficency of the
filtration
EUROVENT
150Pa
EU4
200Pa
EU7
1 MONTH
3 MONTHS
Blowing
(for the G4filters)
(for the G4filters)
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
Reference
G4
F7
Periodicity of the cleaning
6 MONTHS
Cleaning
Washing
(for the G4filters )
Créé par : JC
®
Washing*
(Water + light detergent )
Limited (1 to 4 times)
NO
12 MONTHS
Replacement
Of the filters if needed
Validé par : AR
Aspiration*
Exhaust*
YES
Page 36/49