The following message should appear on the terminal:
The ALARM relay should pull in, holding its "b" contacts open. If the relay pulls in but no
message is received, check the terminal configuration. If neither occurs, turn off the power
and refer to the TROUBLESHOOTING guide.
The equal sign is a prompt indicating that communications with the relay are at Access
Level 0, the lowest of three access levels to the relay. The only command allowed at this
level is ACCESS, which admits you to Access Level 1, as described below.
Type the command ACCESS and press <ENTER>. At the prompt, enter the password
OTTER and press <ENTER>. The prompt = > should appear, indicating that you have
established communications at Access Level 1.
The relay is shipped with demonstration settings which you may inspect using the SHOWSET
command. Type SHOWSET and press <ENTER> to view these settings. The terminal
should display the following:
A complete description of the settings appears under the SET command.
6-2
Maintenance and Testing
Date Code 920326
SEL-267D/167D Instruction Manual