SmartAct N20010, N34010

Wiring Diagrams

N20010 / N34010
TERMINAL STRIP 1
!
N20010-SW2
TERMINAL STRIP 1
!
END SWITCHES
NOTE: Internal end switches S1 and S4 must be connected to the same power source.
connecting cable
supply and signal lines
(must be equipped with spark suppressors)
end switches
(when included)
EN0B-0341GE51 R0307
24 Vac
24 Vdc
1
1~
~
2
2
3Y
0(2)...10 Vdc
3Y
0(4)...20 mA
4U
4U
0(2)...10 Vdc
Connect via safety
isolating transformer!
MODULATING CONTROL
24 Vac
24 Vdc
1
1~
~
2
2
3Y
0(2)...10 Vdc
3Y
0(4)...20 mA
4U
4U
0(2)...10 Vdc
Connect via safety
isolating transformer!
MODULATING CONTROL
CCW (left) 5°
CW (right) 85°
S1
S1
S2
S2
S3
S3
S4
S4
S5
S5
S6
S6
END SWITCHES
terminal
1~
24 Vac ~ / 24 Vdc +
2 ⊥
24 Vac ~ / 24 Vdc -
3Y
0(2)...10 Vdc / 0(4)...20 mA control signal
4U
0(2)...10 V feedback signal
S1
common
S2
normally closed
S3
normally open
S4
common
S5
normally closed
S6
normally open