Allen-Bradley RightSight 42EF Series User Manual page 46

Photoelectric sensors with io-link interface
Table of Contents

Advertisement

Exploring the 42EF IO-Link Parameters
Green LED
Low Intensity
Medium Intensity
High Intensity
42
Location Indicator: This parameter activates the location indication sensor
functionality. When enabled, the sensor user interface (green and orange LEDs)
start flashing synchronously until the operator disables this function. This
parameter is ideal for applications where the operator needs to locate a sensor in
the application where there may be multiple sensors in close proximity.
LEDs Enable: This parameter allows operators to turn OFF or turn ON the
User Interface LEDs (green and orange LEDs). This parameter is ideal for
applications where turning OFF the LEDs is desired to accommodate the
application.
Alignment Mode: This parameter changes the sensor user interface to operate
in alignment mode. The alignment mode uses the green and orange LEDs of the
sensor to visually indicate the strength of the light signal that is reflected back
from the object. Upon entering this mode, the green LED will have a low
visibility if no target is present (or no reflector is seen) and will slowly dim to a
brighter state until a maximum brightness is reached depending on how much
light is the target reflecting back to the sensor. When the maximum brightness is
reached, the orange LED will change duty cycle from 10...90%. The table below
describes the User Interface behavior while operating in Alignment Mode:
Orange LED
Flashing at 1 Hz with 10% duty cycle
Flashing at 1 Hz with 10% duty cycle
Flashing at 1 Hz with 90% duty cycle
The alignment mode can be enabled for an indefinite amount of time or enabled
for limited intervals of 120 and 240 seconds.
Error Count: Displaces the amount of errors.
Device Status: Displaces the status of the device.
Last Event: Displaces the code for the last event initiated by the sensor.
Operation Information: In this section, the operator is able to monitor the
sensor operating hours since inception and power up.
Operating Hours: Since Inception: displays the total operating hours that the
sensor has been running since the first time it was powered ON. This value is not
lost during factory reset. The information displayed in this parameter is
represented in hours.
Operating Hours: Since Inception: displays the total operating hours that the
sensor has been running since the last time the sensor power was cycled. This
value is reset to zero every time the sensor loses power.
Temperature: In this section, the operator is able to monitor the actual,
minimum and maximum internal temperature of the sensor.
Rockwell Automation Publication 42EF-UM001A-EN-P - September 2015
Target State
Not enough light reflection. Signal level is below threshold
Some light being reflected from target. Signal level is below threshold
Optimal amount of light reflected from target. Signal level is above
threshold.
Triggered Status
Sensor Output is OFF
Sensor Output is OFF
Sensor Output is ON