Dometic RMLT 933 Series Installation Manual page 22

Absorber-refrigerator with oven
Hide thumbs Also See for RMLT 933 Series:
Table of Contents

Advertisement

Available languages

Available languages

Installing the refrigerator-oven combination
6.5
Interior oven ventilation (oven without roof flue)
If you are providing the ventilation and flue duct in the vehicle interior, the supply of
fresh air must not be obstructed. Make ventilation holes that allow fresh air to enter
(safety ventilation according to EN 721). A combination of roof and wall ventilation
holes is possible.
Ventilation holes in the lower part may not be more than 100 mm above the interior
floor. The ventilation holes must not be closed under any circumstances. Keep the
grids and covers clean and free of dust.
➤ Make ventilation holes in the vehicle interior with a total cross-section of at least
2
100 cm
.
➤ Make one or more ventilation openings above the oven with a total cross-section
of at least 150 cm
➤ Fit a panel above the oven and a ventilation grille in the panel with
468 mm x 90 mm (fig. 0 1, page 6).
✓ Fresh air enters through ventilation slots into the oven under the door, is heated
and escapes from the oven through ventilation slots in the top of the door
(fig. 0, page 6).
I
NOTE
Check and clean the ventilation holes regularly.
6.6
Installing the ventilation grille
No. in
fig. a, page 7
1
2
3
4
➤ Ensure the installation frame is water resistant (fig. b, page 7).
➤ Insert the installation frame and screw it down tightly (fig. c, page 7).
➤ Fit the ventilation grille (fig. d, page 7).
➤ Insert the slider and lock the ventilation grille with it (fig. d, page 7).
22
2
.
Description
Installation frame
Ventilation grille
Winter cover
Slider
RMLT9xxx
EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents