Input parameters
Table 5- 55
Parameter
Execute
UPS8600_No
Hw_Ident_Head
Battery_In_Param
Structure of UDT_BAT_3P_IN data type
Table 5- 56
Parameter
BatteryType
OperatingTemperature
Capacity
EndOfChargeVoltage
MaxChargeCurrent
TempCoefficient
StartOfPreserveVoltage
EndOfDischargeVoltage
Output parameters
Table 5- 57
Parameter
Battery_Out_Param
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
Data type
Description
Bool
On the rising edge (0 > 1), data at the inputs of the
block is written to the third-party battery.
Int
Number of UPS800 to which this battery is connected
HW_IO
Start address of the UPS8600 submodule (Reference,
system tag: here, "PSU~UPS8600_V1_4_2~Third-
party_battery"). This refers to the UPS8600 submodule
of second UPS8600 connected to the PSU.
UDT_BAT_3P_IN
UDT for general input parameters of third-party battery.
Data type
Description
Byte
Battery type (Pb = 0,
Byte
Operating temperature (Allowed values: 40 to 60)
UInt
Capacity (Allowed values: 0 to 30000)
UInt
End-of-charge voltage at 20° C (Allowed values: 5240 to
5660)
UInt
Maximum charge current (Allowed values: 10 to 250)
UInt
Temperature coefficient (Displayed as mV/K also on OPC
and all other interfaces) (Allowed values: 0 to 100)
UInt
Start preserve change voltage (Allowed values: 4870 to
5660)
UInt
End of discharge voltage (Allowed values: 3920 to 4320)
Data type
Description
UDT_BAT_3P_OUT
UDT for general output parameters of third-party bat-
tery.