Page 3
24 months is valid from the date of sale to the end buyer, but not more than 36 months after delivery from Smarteh. In case of claims within warranty time, which are based on material malfunctions the producer offers free replacement. The method of return of malfunctioned module, together with description, can be arranged with our authorized representative.
Longo programmable controller LPC-2.IR2V 1 ABBREVIATIONS Sorted by order of appearance in document: Infrared Light emitting diode Power Error Dual in-line package Selector...
Longo programmable controller LPC-2.IR2V 2 DESCRIPTION The LPC-2.IR2V is a sensor which consists of the lux sensor for light intensity measurements, temperature sensor, relative humidity sensor and IR receive/transmit for IR communication. Measuring light intensity, temperature and relative humidity provides the information needed for achieving good work conditions.
RC-5 IR protocol receiver Daikin, Toshiba, Hitachi, Panasonic, Mitsubishi IR protocol transmitter 2 diagnose LED Modular frame mounting NOTE: In case of usage Daikin, Toshiba, Hitachi, Panasonic or Mitsubishi IR protocol transmitter, due to various sub protocols, consult with Smarteh.
Longo programmable controller LPC-2.IR2V 4 OPERATION LPC-2.IR2V can be in one of two operational modes - normal or error. When LPC-2.IR2V is in normal mode, module parameters can be read or written via Smarteh IDE software. 4.1 Operational modes Normal Communication with the main module is working.
Page 9
If oIrProtocolSel is "0": When LPC-2.IR2V receives an IR command, value of iIrCmdRecNum corresponds to the number of the IR learned command. Value is set back to 0 after next communication cycle with main module or after approximately two seconds regardless communication.
Page 10
Longo programmable controller LPC-2.IR2V is "1": When LPC-2.IR2V receives an IR command, value of iIrCmdRecNum corresponds to the number described below in binary code which includes toggle bit, address code and data code of the RC-5 protocol. When button is released, value gets to 0 after next communication cycle with main module or after approximately two seconds regardless communication.
In this example, switches must be set to setting "learning mode for command 15". Once this is done, LPC-2.IR2V is ready to receive the IR command from the remote controller and store it to internal memory under command 15.
Page 13
Longo programmable controller LPC-2.IR2V Table 2: K1 K1.1 Ground K1.2 7 .. 30 V DC Power supply input K1.3 Standard RS-485 A Data receive/send line A K1.4 Standard RS-485 B Data receive/send line B Table 3: LEDs ON: RS-485 communication fault...
Master ● Frames of other vendors most probably suits as well, but they were not verified by Smarteh. Before installation verify compatibility of non listed frames. Module housing has a fin on each side, which can be easily removed with knife cutter or pliers. This adaptation enables housing to be inserted in various frame formats.
3. Put the LPC-2.IR2V in mounting frames, with ventilation slots positioning downwards. 4. Cover LPC-2.IR2V with cover plate. LPC-2.IR2V is connected to main module with interconnection cable (e.g. SSK, ICM-7) which must be ordered together with LPC-2.IR2V. When more modules (e.g. LPC-2.CR1, LPC-2. CH1, LPC-2.DP1,..) are connected to main module, splitter (e.g.
Label 2 descriptions: 1. S/N: IR2V-S9-1900000003 is the serial number. IR2V – short product name, • S9 – user code (test procedure, e.g. Smarteh person xxx), • 1900000003 – year and current stack code, • 19 – year (last two cyphers), •...
Longo programmable controller LPC-2.IR2V 6 TECHNICAL SPECIFICATIONS Table 6: Technical specifications Power supply from main module Interconnection connector type RJ-12 6/6 Power consumption 0.5 W Light intensity measurement range 0 .. 2990 lux IR frequency carrier 38 kHz IR max. pulse length in protocol used for...
Longo programmable controller LPC-2.IR2V 7 SPARE PARTS For ordering spare parts following Part Numbers should be used: LPC-2.IR2V Infrared transceiver and light sensor LPC-2.IR2V P/N: 225IR218V01002 LPC-2.RC1S remote control LPC-2.RC1S P/N: 225RC116001001 Interconnection cable ICM-x P/N: 203ICMxxxxxxxx Splitter SPL-2 (1/8)
Longo programmable controller LPC-2.IR2V 8 CHANGES The following table describes all the changes to the document. Date Description 12.04.19 Technical update. 29.03.19 Technical update. 18.01.17 Technical update. 16.11.16 Added IR data. 30.10.16 The initial version, issued as LPC-2.IR2V User Manual.