24-10239-480 Rev. F
Reference – These signals are referenced to logic ground (COM).
Protection – Each signal has a 30 volt transient voltage suppressor
between it and system ground.
Relay Output Points
Description of Signals – NC, NO, and COM are the three connections to
a single pole, double throw relay. The following are the relay outputs:
Reader 1 Strike
Reader 1 Shunt
Reference – The relay is a dry contact relay rated at 1 A at 24 VDC/
VAC, 25 VA maximum.
Reader Power
Description of Signals – 250 mA at 12 VDC is provided for each reader.
Protection – There is a 750 mA PTC re-settable fuse.
Network Connection
RJ45 connector – Use this connector to connect the S321-IP to the
network. The S321-IP communicates with the P2000 server via 10/
100Base-T Ethernet, using the TCP/IP protocol.
C
R
ABLE
EQUIREMENTS
This table describes the recommended cable to use when wiring the S321-IP.
Description
Recommended Cable Type Maximum Segment Length
S321-IP to Power
Listed, 18 AWG, hook-up
1
Supply
wire
S321-IP to Host
Listed, Category 5, 24 AWG,
solid, 2 pair or 4 pair type.
Door Contact
Belden 8442, 1 twisted,
unshielded pair, 22 AWG
Door Strike and
Belden 9740, 1 twisted,
Shunt
unshielded pair, 18 AWG
Reader 2 Strike
Reader 2 Shunt
Wire should fit within the enclosure.
354 ft (100 m). Cable, RJ45 connector,
and RJ45 crimp tool to be supplied by
customer.
500 ft. (152 m)
Depends on power requirements of the
door strike. Do not reduce voltage to
the strike more than 10% over the 18
AWG wire, measured when energized.
7