In the above three steps, the reading measured in each step is the
value of the two series grounding resistance. In this way, we can
easily calculate the value of each grounding resistance:
From:
We get:
This is the grounding resistance value of the grounding body R
To facilitate the memory of the above formula, these three
grounding bodies scan be viewed as a triangle; then the measured
resistance is equivalent to the value of the resistance values of the
adjacent edges plus or minus resistance value of the opposite
sides, and divided by 2.
As the reference points, the grounding resistance values of the
other two grounding bodies are:
RB=R1-RA
RC=R3-RA
Earth Tester
Test Loop
Carrying Case
User's Manual
R1=RA+RB
RA=(R1+R3-R2)÷2
IX. Bill of Loading
R2=RB+RC
-24-
R3=RC+RA
1 piece
1 piece
1 piece
1 piece
.
A
Need help?
Do you have a question about the ETCR2000+ and is the answer not in the manual?