2.7.27 LIVE and NEUTRAL supply external interface – P/N NXO2INT
LIVE PL 1
NEUTRAL PL2
2.7.28 Oxygen probe connection (optional Oxygen Probe Interface unit)
Bussman S504 series
PN GMA-5
5 AMP (Fast Acting)
( to protects transformer primary DC
circuit)
Alternate Source:
Mouser Electronics : PN 504-GMA-5
NOTE: 4-20mA O
WARNING
Incorrect setting of the Supply Voltage Links WILL damage or destroy the unit.
MAX 3A
LIVE
NEUTRAL
input from non-Fireye O
2
The LIVE and NEUTRAL supplies must be connected
using multi-strand single conductor (core) PVC insulated
16 AWG (19/0.3mm) wire. The live connection should be
fused with a maximum rating of 3A.
probe. See sections 30.1 and 30.2
2
53
Bussmann - S504 series
P/N GMD-630 (TIME Delay) for 115V
P/N GMD-315 (TIME Delay) for 230V
( to protect 24V circuit
Alternate Source::
Mouser Electronics
PN 504-GMD-630mA
PN 504-GMD-315mA
Termination for
screens from
Oxygen Probe (screw)
PL 7 0v
Common ( - ) see note
PL 6 I/P 2
4 + 20mA (+) see note
PL 5
N/A future use
PL 4 CANbus –
PL 3 CANbus +
PL 2 Neutral
PL 1 Live
Ground
(Earth) (screw)