Menu overview
Menu description
Menu buttons
18
Default view
Example
OK
48
rH50
o
COF
EFOF
SIOF
Update to latest software version, if the menu looks different.
Code Function
rH
Relative
humidity (%)
°C
°Celcius
(accessory only)
EF
Extractor fan
(accessory only)
SI
Service Interval
(weeks)
OK
Press and hold OK button for 3 sec to enter menu mode
Toggle Menu Page / change value
Note: If no button is pressed for 10 seconds it will return to Standard view.
OK
OK
OK
OK
Default
Value
Description
value
range
50
40-99 The unit will start dehumidifying, when the sen-
sor measures a relative humidity higher than the
set value. (Note the +/- 2% hysteresis)
OF
5-34 The el/water heating coil (accessory) will start
to heat, when the temperature is lower than the
(OFF)
set value. (Note the +/- 2 °C hysteresis)
OF
40-99 The extractor fan (accessory) will start, when the
humidity is higher than the set value, complete-
(OFF)
ly independent of the dehumidifier. The value is
measured in % relative humidity.
(Note the +/- 2% hysteresis)
OF
1-99 When the Service Interval function is enabled,
the unit will display SEr, when it is time for
(OFF)
service.
Operation: Control panel
<