iv) The Sensor Assembly should not be placed under or within 7.m of power or telephone wires.
v) Height of objects within 7.m of the sensor should be at most 1.5.m tall.
vi) Minimum 7.m distance applies to objects with a height comparable to the sensor, taller objects
will need to be further away to prevent shielding of the sensor. Recommended distance is 2/3
the height of the object in addition to the 7.m separation.
The Sensor should only be installed in locations conforming to the "Approved Sensor Locations"
requirements.
Range Extender Installation
As Range Extenders do not have any lightning event
detection capability they are not subject to the same
location restrictions as Sensors. Range Extenders will need
to be placed in positions that allow <1km line of sight to the
Console, Sensor or another Range Extender.
Cabling installation, Alarm relay plug and socket, mounting,
power supply, siren and solar panel installation instructions
are as shown in Sensor Installation points iii (without sensing
antenna or earthing cable), iv, v, viii and ix respectively.
Document 36 II LWS-MKIII, pub V5 © Copyright 2012 LPI
Page 21