Auto Operation; When Unit Is Stopped Control Mode - Mitsubishi Electric City Multi Series Technical & Service Manual

Ceiling cassettes
Hide thumbs Also See for City Multi Series:
Table of Contents

Advertisement

8-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
RETURN SELECT
MENU
HOLD
.
Control Mode
1. Initial value of
HEAT mode for room temperature < Set temperature
COOL mode for room temperature ] Set temperature
operation mode
2. Mode change
Room temperature ] Set temperature + 3°F or 3 minutes have passed.
Room temperature [
3. COOL mode
Operates as it would in COOL operation.
4. HEAT mode
Operates as it would in HEAT operation.

8-6. WHEN UNIT IS STOPPED CONTROL MODE

Control Mode
1. Drain pump
1-1. Drain pump control
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (FAN).
2
control judges the sensor is in the water.
1-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by
OCH610G
<How to operate>
1 Press ON/OFF button.
2 Press [F1] button to display AUTO.
3 Press [F2] [F3] button to set the set temperature.
ON
OFF
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display AUTO.
3 Press the TEMP. button to set the set temperature.
Control Details
Control Details
NOTE: The settable temperature range varies with the model
of outdoor units and remote controller.
NOTE: The set temperature changes 1°F when the
button is pressed one time. Automatic 67 to 83°F
30
or
Remarks
Remarks
• Operates as it would
in COOL operation.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents