Mitsubishi Electric City Multi Series Technical & Service Manual page 36

Ceiling cassettes
Hide thumbs Also See for City Multi Series:
Table of Contents

Advertisement

Switch
Pole
SW11
SW12
1s digit
0
address
setting
SW12
10
10s digit
address
setting
SW14
0
SW14
Connection
No.
setting
1
Setting the ceiling height
2
Setting the ceiling height
SW21
3
Setting the number of air outlet
Function
Setting
4
Setting the number of air outlet
5
Setting for optional parts
6
Not used
<Table E>
SW21-1
SW21-3
OFF
4 direction
SW21-4
ON
SW21-3
OFF
3 direction
SW21-4
OFF
SW21-3
ON
2 direction
SW21-4
OFF
Note: The setting with
OCH610G
Function
SW11
0
1
Depending on the combination
of SW21-1 and SW21-2.
Refer to the <Table E> below.
Depending on the combination
of SW21-3 and SW21-4.
Refer to the <Table E> below.
Option
Not used
PLFY-EP06/08/12/15/18/24/30NEMU-E
PLFY-EP18NEMU-E1
Silent
Standard
SW21-2
SW21-1
SW21-2
OFF
ON
OFF
OFF
8.2 ft [2.5 m]
8.9 ft [2.7 m]
8.9 ft [2.7 m]
9.8 ft [3.0 m]
9.8 ft [3.0 m]
10.8 ft [3.3 m]
indicates the initial setting; To change it to other than
Operation by switch
Effective
timing
ON
OFF
Address setting
should be done
when M-NET
remote controller is
being used.
Before
power
supply
This is the switch
ON
to be used when
the indoor unit is
operated with R2
series outdoor unit
as a set.
Under
suspension
Standard
Not used
High ceiling
Silent
SW21-1
SW21-2
SW21-1
ON
OFF
OFF
11.5 ft [3.5 m]
8.9 ft [2.7 m]
11.5 ft [3.5 m]
9.8 ft [3.0 m]
11.5 ft [3.5 m]
10.8 ft [3.3 m]
, switch setting is necessary.
36
Remarks
Indoor controller board
<Initial setting>
SW12
SW11
0
0
Indoor controller board
<Initial setting>
SW14
0
Indoor controller board
<Initial setting>
ON
OFF
1 2 3 4 5 6
PLFY-EP36/48NEMU-E
Standard
SW21-2
SW21-1
SW21-2
SW21-1
ON
OFF
OFF
ON
10.5 ft [3.2 m]
14.8 ft [4.5 m]
11.8 ft [3.6 m]
14.8 ft [4.5 m]
13.1 ft [4.0 m]
14.8 ft [4.5 m]
Continue to the next page