H.Where ducted Fans are used to handle moisture-laden air, a
condensation trap should be fitted. Horizontal ducts should
be arranged to slope slightly downwards away from the Fan.
I. This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they
have been given supervision or instruction concerning use of
the appliance by a person responsible for their safety.
J. Young children should be supervised to ensure that they do
not play with the appliance.
A.

INSTALLATION.

The unit is designed as an in-line duct fan to be positioned between lengths of ducting. Short duct runs terminating close to the
fan (i.e. within 1.5m) must incorporate suitable guards unless the fan is mounted higher than 2.1m above the floor. If flexible
ducting is used it should be fully extended to obtain the best results. Position the fan at the highest point on the system with both
ducting runs sloping downwards from this point. The airflow direction is indicated on the rating label with an arrow pointing in the
direction of the airflow. In circumstances where an excessive amount of moisture is present in the air then a condensation trap
should be installed. (Refer to Fig 15 for overall fan dimensions and fixing hole positions). When siting the appliance ensure that
there is sufficient space to allow access for any servicing and maintenance.
To gain access to the mounting holes, proceed as follows: -
A.
Using a cross-headed screwdriver, release the two blue plastic clips by undoing the two bolts as shown in Fig 1. Slide
out motor impeller assembly, see Fig 2.
B.
The fan can now be mounted at any angle, using the holes provided Fig 3,4,5,6 & 15
C. Once the base is securely fixed, slide the motor impeller assembly back, as shown in Fig 7. Replace the screw and
tighten to lock the assembly together Fig 8.