Safety And Guidance Notes - Vent-Axia ACM100 B Installation And Wiring Instructions

In-line mixed flow fans 220-240v 50hz
Table of Contents

Advertisement

Installation and Wiring Instructions for the ACM IN-LINE MIXED FLOW FAN range.
DO NOT install this product in areas where the following may
be present or occur:
• Excessive oil or a grease laden atmosphere.
• Corrosive or flammable gases, liquids or vapours.
• Ambient temperatures higher than 40°C or less than –5°C.
• Possible obstructions which would hinder the access or
removal of the Fan.
• Sudden ductwork bends or transformations close to the Fan.

SAFETY AND GUIDANCE NOTES

A. All wiring to be in accordance with the current I.E.E.
Regulations, or the appropriate standards of your country
and MUST be installed by a suitably qualified person.
B.The Fan should be provided with a local double pole isolator
switch having a contact separation of at least 3mm.
C.Ensure that the mains supply (Voltage, Frequency, and
Phase) complies with the rating label.
D.The Fan should only be used in conjunction with the
appropriate Vent-Axia products.
E. It is recommended that the connection to the fan connecter
terminals is made with flexible cable.
F. When the Fan is used to remove air from a room containing a
fuel-burning appliance, precautions must be taken to avoid
back-flow of gases into the room from the open flue of gas or
other appliance. Ensure that the air replacement is adequate
for both the fan and the fuel-burning appliance.
G. The Fan should not be used where it is liable to be subject to
direct water spray for prolonged periods of time.
IMPORTANT: READ THESE INSTRUCTIONS
BEFORE COMMENCING THE INSTALLATION
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acm100 tAcm125 bAcm125 tAcm150 bAcm150 tAcm160 b ... Show all

Table of Contents