Troubleshooting - Alarm History - Emerson Copeland Eazycool OMTE-90D-TFD Application Manuallines

Large outdoor condensing unit
Table of Contents

Advertisement

2.17 Troubleshooting – Alarm history
The controller records the total number of alarm activations (max 50) in the alarm menu (see
Appendix 3).
Action
Enter menu
Waiting for action
Enter section list
Select active alarm
code from list
Select the alarm to
see the detailed rtC
information
Select detailed
information from
active alarm list
Exit menu
Table 16: How to check the alarm list
C6.1.9/0219/E
Key or display
Notes
Push and release the ALR key.
The menu to change the section will be entered. The
SEC
alarm list section is active.
Press SET to confirm. The following list will be
available to select the proper network function.
Scroll the list of active alarms by alarm number (letter
+ number, A01-A50).
or
Press
Press
Enter the sub menu with alarm time details.
With the rtC activated:
or
Note: The clock info indicates the START time of the
alarm.
Without the rtC activated:
The COn (hours) parameter is displayed.
Press
To exit: press
pressing any key.
Press
seconds without pressing any key.
to see the alarm name or code.
to see the next active alarm.
The Hur (hour) parameter is displayed.
Press
to see the alarm hour.
Press
: Min is displayed.
Press
to see the alarm minute.
Press
: dAy is displayed.
Press
to see the alarm day.
Press
: MOn is displayed.
Press
to see the alarm month.
Press
: YEA is displayed.
Press
to see the alarm year.
to see the compressor working hours.
or wait for 15 seconds without
simultaneously or wait for about 10
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents