P&I Diagram For Omte-152D Units; Figure 8: P&I Diagram For Omte-152D - Emerson Copeland Eazycool OMTE-90D-TFD Application Manuallines

Large outdoor condensing unit
Table of Contents

Advertisement

2.7.8
P&I diagram for OMTE-152D units
Figure 8: P&I diagram for OMTE-152D
Position
B1
PT P1 Pressure transmitter suction (AI1)
B2
Condensing pressure transmitter (AI2)
B3
DLT Discharge line temperature sensor (AI3)
B6
Ambient temperature probe (AI6)
B7
Liquid receiver with liquid level watch
B10
PSL >> LP Mechanical low-pressure switch PS1 (PSL)
B11
TT >> DLT Discharge line thermostat 130°C compressor 1
B12
TT >> DLT Discharge line thermostat 130°C compressor 2
B21
PSH >> High-pressure cut-out device compressor 1
B22
PSH >> High-pressure cut-out device compressor 2
E1
Crankcase heater compressor 1
E2
Crankcase heater compressor 2
M1
High-efficiency Digital Scroll compressor ZBD family
M2
High-efficiency standard Scroll compressor ZB family
M3
High-efficiency EC fan
M4
High-efficiency EC fan
Y1
Digital control solenoid valve
Y3
TraxOil active oil management device compressor 1
Y4
TraxOil active oil management device compressor 2
Table 6: Legend of the P&I diagram for OMTE-152D units
C6.1.9/0219/E
Description
Comments
PPR15
PPR30
NTC 86k
NTC 10k
LW4-L120 Alco
PS1-A3A Alco
PS3-W6S Alco
PS3-W6S Alco
Compressor 1
Compressor 2
FN071-ZIQ
FN071-ZIQ
OM3-CCE
OM3-CCE
9