Figure 19: Heat recovery implementation

2.15 Pumpdown – General
CAUTION
System pressure below atmospheric pressure! Compressor damage!
Never operate the system below atmospheric pressure. There is a risk of
malfunction of the controller in deep vacuum operation which can cause
compressor damage.
Pumpdown functionality is not provided by the XCM25D controller for condensing unit models OMTE
or OLTE covered in these guidelines.
2.16 Reset to factory settings – Emerson "Hot Key"

2.16.1 How to save factory settings or user settings

There is no way to reset the XCM25D controller to factory settings other than with additional
equipment. Emerson recommends using the Emerson "Hot Key" (not part of the standard delivery)
to save the factory settings at initial power up. The same hot key can also be used to save user
settings.
By means of a special programming software (Emerson Wizmate) and corresponding hardware
(Emerson Prog-Tool), the user can:
preprogram hot keys
copy hot keys
change parameter levels
compare parameter lists
For further information please visit our website at
local Application Engineering representative.
2.16.2 Applicable hot key for OM & OL units with XCM25D controller
The Emerson "Hot Key" DK00000300 can be used for uploading and downloading of parameter lists.
Copeland ident number 3226456.

Figure 20: Emerson "Hot Key"

C6.1.9/0219/E
www.climate.emerson.com/en-gb
or contact your
21