VIPA HMI
HB160 | PPC | 67S-PNL0 | en | 18-18
n
Proof the correct fixing of the lead isolation.
Data lines must be laid isolated.
Analog lines must be laid isolated. When transmitting signals with small ampli-
tudes the one sided laying of the isolation may be favourable.
Lay the line isolation extensively on an isolation/protected earth conductor rail
directly after the cabinet entry and fix the isolation with cable clamps.
Make sure that the isolation/protected earth conductor rail is connected impe-
dance-low with the cabinet.
Use metallic or metallised plug cases for isolated data lines.
n
In special use cases you should appoint special EMC actions.
Consider to wire all inductivities with erase links.
Please consider luminescent lamps can influence signal lines.
Create a homogeneous reference potential and ground all electrical operating sup-
n
plies when possible.
Please take care for the targeted employment of the grounding actions. The
grounding of the PLC serves for protection and functionality activity.
Connect installation parts and cabinets with your PLC in star topology with the
isolation/protected earth conductor system. So you avoid ground loops.
If there are potential differences between installation parts and cabinets, lay suffi-
ciently dimensioned potential compensation lines.
Basic rules for the EMC-equitable assembly of installations
Installation guidelines
53