CALEFFI LEGIOMIX 6000 series Installation And Commissioning Manual

CALEFFI LEGIOMIX 6000 series Installation And Commissioning Manual

Electronic mixing valve
Hide thumbs Also See for LEGIOMIX 6000 series:

Advertisement

LEGIOMIX ® electronic mixing valve
© Copyright 2017 Caleffi
INSTALLATION AND COMMISSIONING MANUAL
configurable via keypad, or local or remote computer. Depending on the type of system and habits of
the user, temperature levels and operation times can be programmed as desired. In addition, it comes
standard with monitoring and remote control connections.
The LEGIOMIX ® 6000 series electronic mixing valves meet the requirements of ANSI/NSF 372-2011
and are certified to ASSE 1017, CSA B15.3, UPC, IPC, Low Lead Laws and listed by ICC-ES for use
in accordance with the U.S. and Canadian plumbing codes.
Product range
6000 series Electronic mixing valve with programmable thermal disinfection and male NPT
connections..............................................................................................sizes 1", 1¼", 1½" & 2"
6000 series Electronic mixing valve with programmable thermal disinfection and sweat
connections..............................................................................................sizes 1", 1¼", 1½" & 2"
NA10520 Modbus-to-BACnet gateway
www.caleffi.com
Function
The electronic mixing valve is used in centralized
systems that produce and distribute domestic hot
water. It maintains the temperature of the domestic hot
water delivered to the user when there are variations in
the temperature and pressure of the hot and cold water
at the inlet or in the draw-off flow rate. The LEGIOMIX ®
electronic mixing valve provides precise temperature
control over very low and very high flow rate demand,
minimal pressure drop with a ball valve control element,
automatic self-cleaning to prevent scale formation and
easy-to-use digital interface with data logging, alarming
and status indication. The LEGIOMIX ® electronic mixing
valve is furnished with a controller with LCD user
interface that provides a set of programs for circuit
thermal disinfection to kill Legionella. The controller is
1
H0002997
6000 series

Advertisement

Table of Contents
loading

Summary of Contents for CALEFFI LEGIOMIX 6000 series

  • Page 1 H0002997 www.caleffi.com LEGIOMIX ® electronic mixing valve 6000 series © Copyright 2017 Caleffi INSTALLATION AND COMMISSIONING MANUAL Function The electronic mixing valve is used in centralized systems that produce and distribute domestic hot water. It maintains the temperature of the domestic hot...
  • Page 2: Safety Instruction

    SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD. CAUTION: All work must be preformed by qualified personnel trained in the proper application, installation, and maintenance of systems in accordance with all applicable codes and ordinances.
  • Page 3: Consigne De Sécurité

    CONSIGNE DE SÉCURITÉ Ce symbole d'avertissement servira dans ce manuel à attirer l'attention sur la sécurité concernant instructions. Lorsqu'il est utilisé, ce symbole signifie. ATTENTION! DEVENEZ ALERTE ! VOTRE SÉCURITÉ EST EN JEU ! NE PAS SUIVRE CES INSTRUCTIONS PEUT PROVOQUER UN RISQUE DE SECURITE. ATTENTION: Tous les travaux doivent être effectués par du personnel qualifié...
  • Page 4: Technical Specifications

    Technical specifications Valve body Materials: - Body: DZR low-lead brass - Ball: low-lead brass, chrome-plated - Hydraulic seals: peroxide-cured EPDM Max working pressure (static): 150 psi (10 bar) Max. inlet temperature: 212°F (100°C) Temperature gauge scale: 30 - 210°F Suitable fluids: water Max.
  • Page 5: Characteristic Components

    Mixing valve performance Accuracy: ± 3º F (± 2º C) Max. operating differential pressure (dynamic): 75 psi (5 bar) Max. ratio between inlet pressures (H/C or C/H): Recommended Flow Rates (gpm/lpm) Size 1" 1¼" 1½" 2" Minimum* 3.1 / 11.7 4.4 / 16.6 6.6 / 25 8.8 / 33.3 Maximum...
  • Page 6 Operating principle The electronic mixing valve mixes hot water from storage and cold water from the main supply to maintain a constant controlled set temperature of mixed water at the outlet. The controller measures the temperature of the mixed water at the valve outlet with temperature sensor and modulates the mixing valve position to maintain the desired set temperature.
  • Page 7 FLUSH VALVES Relay 4 (reduce temperature) 2nd THERMOSTAT Relay 3 (aquastat) Relay 2 ALARM (unsuccessful disinfection cycle) Relay 1 RECIRC PUMP (disinfection) Mixed °C Return °C TUESDAY 1 / 02/ 2017 ADJUSTMENT IN PROGRESS Shock Menu OPTIONAL MODBUS/ BACNET GATEWAY 24 VAC RELAY 1, 2, 3, 4 24 VAC FLOATING CONTROL...
  • Page 8: Back Panel

    Back panel To remove the electrical wiring base, turn it round and extract it from its housing. Mixing valve fuse Appliance fuse 1 A - 250 V delayed 80 mA - 250 V delayed Closes PIN code Common disabling button Opens Earth Earth...
  • Page 9: Temperature Sensor Resistance Values

    Temperature sensor resistance values ºF ºC Ω ºF ºC Ω ºF ºC Ω ºF ºC Ω 100254 15310 3049 72937 11882 2489 53669 9297 2044 39919 7333 1688 32648 5827 1402 26100 4664 1171 19900 3758 Location of cable connectors To remove the electrical wiring base, turn it round When making...
  • Page 10 Connection cable cross-sections and lengths for circuit board wiring Unsheathing (in/mm) Cable seal No. Cable type including stripping 3 x 1 5 / 130 6 x 0.75 6 / 150 2 x 0.75 8.25 / 210 2 x 0.75 8.25 / 210 3 x 0.75 8.25 / 210 2 x 1.5...
  • Page 11 Front panel Mixed °C Return °C THURSDAY 10/12/ 2017 ADJUSTMENT RUNNING Shock Menu Cut the wires of the auxiliary microswitch (if not used) and insulate electrically before wiring (colors: white, green and red). 1. LCD display* 5. LED display: Treturn - return water 2.
  • Page 12: Led Indicators

    Indication description Indications on LED display LED indicators 3 LED displays on the front of the controller The following LED indicators are located on the front show the clock time and termperature of the of the controller: mixed outlet water temperature and return tem- perature sensors at all times.
  • Page 13: Operating Status

    Operating status Depending on the times and the programs that have been set, the controller may be in one of the following operating modes.: • Adjustment; • Disinfection; • Flushing; • Thermal shock (this function has #1 priority over other modes) In the event of trouble due to the LEGIOMIX ®...
  • Page 14 Confirming disinfection If, within the time span (Time OFF - Time ON), the actual disinfection time reaches tDIS is greater than the set tMIN, the disinfection is concluded with a positive outcome. It automatically exits this status and returns to the adjustment (modulating) mode. If the sufficient time tDIS is not reached, the disinfection phase ends at Time OFF.
  • Page 15 Reset On the back panel, there is a specific reset button, in case it is necessary to retore the initial settings. If the date and time are not set after the reset, the controller will operate according to the factory default settings. Actuation relays The circuit board and terminals show the relay contacts used to manage auxiliary equipment and to report alarms.
  • Page 16 Programs The operation of the controller during disinfection can be set according to different programs, selected depending on the type of system and management of the system. Set the program, and the day and time to turn on and turn off disinfection, in parameters in SETTINGS. Program 0 Features continuous mixed outlet water temperature modulation with automatic disinfection in a time band that can be set.
  • Page 17: Thermal Disinfection

    Thermal disinfection The temperatures and corresponding disinfection times for the network must be chosen according to the type of system and the related intended use. The following criteria is generally followed, guided by..T = 160º F (70º C) for 10 minutes T = 150º...
  • Page 18: Remote Control

    Contact Caleffi for list of registers (points) for mapping LEGIOMIX ® information to ModBus. Configuation, mapping, hardware (routers, modem, etc.), and software are customer/user responsibility. Code NA10520...
  • Page 19: Operating Parameters

    Operating parameters The operating parameters can be set in the appropriate menus, and are summarized below: Summary of parameters. Setting ranges and factory (default) configuration. Factory (default) Parameter Description Setting Range configuration I-E-F-D-ES-P-NL- Language Language shown on LCD display ENGLISH SL-HR-SR-RO Date/Time For Disinfection phase and log entries...
  • Page 20: Thermal Shock

    100 sec in 2 sec steps Consult Caleffi otherwise. (This is NOT motor stroke time) Ball rotation cycle to clean deposit formation for ANTI-CLOG efficient operation. To deactivate enter release code 5566 and confirm with ON-OFF.
  • Page 21 The “log” is a FIFO (First In - First Out, loop buffer) that is continually updated and records parameters relating to adjustment and disinfection phases that occurred during the day. Data are stored for the last 40 days, after which the data for the first day are overwritten, etc. The hourly average mixed outlet and return water termperatures are save to Eeprom every hour, and alarms are saved at the time they occur.
  • Page 22: Battery Charging

    Deleting the Log HISTO RIC 06/04/2005 HISTO RIC 06/04/2005 HISTORIC 06/04/2005 tDIS 060’ PGRM 1A H 01 02 03 04 05 06 H 07 08 10 11 12 TR MAX 130 ° TR MIN 120 ° TA --- --- --- --- --- TA 120 120 120 122 119 123 ALARM -- - 4 5-7-...
  • Page 23 Menu structure table L e v e l 1 L e v e l 2 L e v e l 3 B u t t o n fu n c t io n s L A N G U A G E S E L L A N G U A G E S E L E - F - D - E S - P - NL - DOWN + OK...
  • Page 24 Operability after alarm (page 1) Type of alarm P rogram Indic ation by alarm L E D Indic ation by L E D dis play Dis play on L C D R ec ording in log 0 1A 1B 2 G eneric alarm LE D comes Alarm shown on LE D display.
  • Page 25 Operability after alarm (page 2) R elay s tatus Operating s tatus R elay 2 closed (if no alarms, In safe mode. Mixing valve closes, i.e. only cold water enters. the relay is normally open). Adjustment or disinfection or thermal shock is cancelled. All alarm indications are cleared when the cause of the alarm has been removed.
  • Page 26: Plumbing Installation

    Always install strainers of appropriately sized capacity at the inlet from the water main supply. Caleffi LEGIOMIX ® electronic mixing valves must be installed as shown below, conforming to applicable codes, and installed either vertically or horizontally, but the actuator ∞...
  • Page 27 Alarm management To make it easier to resolve any functional faults that occur after installation and commissioning, the controller is configured so that faults are indicated by special alarms and the appropriate action is taken. The cause of the alarm is shown on the LCD display. If the alarm does not inhibit all the functions, the alarm screen will alternate with controller status screen.
  • Page 28 THE LEGIOMIX ® CAN HELP REDUCE BACTERIA IN DOMESTIC HOT WATER RECIRCULATION SYSTEMS, HOWEVER DUE TO SYSTEM-DEPENDENT VARIABLES, 100% ERADICATION CAN NOT BE GUARANTEED. CALEFFI IS NOT RESPONSIBLE FOR ANY DAMAGES, CONSEQUENTIAL OR OTHER, THAT MAY ARISE FROM LEGIONELLA ILLNESS WHEN USING THE LEGIOMIX ®...